Hex coupling, Coupling, On p – HP 403349-003 User Manual

Page 77

Advertising
background image

Removal and replacement procedures 77

9.

Open the ball valves on the hose assemblies.

10.

Confirm that water is flowing through the ball valve couplers, by touching the couplers. The couplers
should be cold.

11.

Replace the hose insulation over the couplers.

12.

Replace the air deflector plate ("

Replacing the air deflector plate

" on page

34

).

13.

Replace the fan unit ("

Replacing the fan unit

" on page

52

).

14.

Complete the operation checklist (on page

111

).

HEX coupling

The three HEX couplings are located at the rear of each HEX unit iinside the MCS unit.

The following tools are required for installation:

T-25 Torx driver

Water hose fitting wrench (included with your original MCS unit)

Counter hold wrench (included with your original MCS unit)

Flathead screwdriver

Utility knife

Advertising