Installer self-test, Caution, Installer system test – Honeywell CHRONOTHERM T8602D User Manual

Page 10: Iv deluxe programmable thermostats

Advertising
background image

T8600D, T8601D AND T8602D CHRONOTHERM

®

IV DELUXE PROGRAMMABLE THERMOSTATS

68-0164—1

10

M10315

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Daylight

Time

Copy

AM

DST

Tue

Set Day/Time

NOTE:

If the current time is Daylight Savings Time,
press Daylight Time until DST is displayed.

M10316

Time

Set Program

System

Fan

Run

Program

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Copy

Auto

System

Fan

Wake

Room

AM

DST

Tue

Heat

Aux Ht

Heat

Auto

System

Fan

Off

Auto

Wake

Mon

Wait

In

Room

Outdoor

%Humid

Auto

Sav

AM

PM

Hold for

Cool

Repl Batt

On

Recovery

DST

Cool

TueWedThuFriSatSun

LeaveReturnSleep

M10345

Set Program

Set Day/Time

Start Time

Temporary Setting Enrg

Em Heat

Em Ht

INSTALLER SYSTEM TEST

Use the Installer System Test to check the thermostat operation.
Refer to Table 7 for a list of the available system tests.

To start the system test:

CAUTION

The minimum off time for compressors is bypassed
during the Installer System Test. Equipment damage
can occur if the compressor is cycled too quickly.

Press and hold the increase

and

decrease keys, at the

same time, until 10 appears. All segments of the display are
displayed for three seconds before 10 appears. See Fig. 10
and 11.

M10257A

TEST NUMBER

Fig. 10. Display of all the segments of the LCD.

Refer to Table 8 for the directions and results of the specific
tests.

NOTE:

Press Time

to advance to the next test and Time

to go to the previous test. Press Run Program to

exit the system test.

Table 8. Installer System Test Options.

Fig. 11. Display of test number.

4. Press Run Program.

Table 7. Tests Available in Installer System Test.

Key to Press

Test

Number

Description

Heating Equipment System Test

Time

10

Enter heating equipment system test.

11

Heat comes on. When Installer Setup number 2 is 1, the system fan is also energized.

10

Heat and system fan turn off.

Cooling Equipment System Test

Time

30

Change from heating to cooling equipment system test.

31

Cool and system fan come on.

30

Cool and system fan turn off.

Fan Equipment System Test

Time

40

Change from cooling to fan equipment system test.

41

Fan comes on.

40

Fan turns off.

Key Operation System Test

Time

60 2

Change from fan to key operation system test.

Test

Number

System Test Description

10-19

Heating equipment can be turned on and off

30-39

Cooling equipment can be turned on and off

40-49

Fan equipment can be turned on and off

60 0 to

60 19

Keyboard keys test

70-79

Thermostat information including date code and
software versions are displayed