T8600D, T8601D AND T8602D CHRONOTHERM

®

IV DELUXE PROGRAMMABLE THERMOSTATS

68-0164—1

8

Table 6. Thermostat Installer Setup Options.

(continued)

Installer Setup

Number (Press

Time

key to

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

change)

Display

Description

Display

Description

Setting

Not used

1

Fan operation

a

2

0

Conventional
applications where
equipment controls fan
operation in heat mode

1

Heat pump or electric heat
applications where thermostat
controls fan operation in heat
mode

Not used

3

Heating cycle
rate

4

6

6—6 cph used for
conventional heat

1, 3 or 9

1—1 cph used for radiant floor

heat, gravity system

3—3 cph used for hot water

systems or high efficiency
furnaces

9—9 cph used for electric heat

systems

Not used

5 thru 11

System setting
adjustment

12

1

Manual changeover

0 or 2

0—Auto changeover
2—Fixed auto changeover

Adaptive
Intelligent
Recovery™
control

13

0

Adaptive Intelligent
Recovery™ control is
activated (system
starts early so setpoint
is reached by start of
program period)

1

Conventional recovery (system
starts recovery at programmed
time)

Degree
temperature
display

14

0

Temperature is
displayed in °F

1

Temperature is displayed in °C

Not used

15

Clock format

16

0

12-hour clock format

1

24-hour clock format

Not used

17 and 18

Extended fan
operation in
heating

a

19

0

No extended fan
operation after the call
for heat ends

1

Fan operation is extended 90
seconds after the call for heat
ends.

Extended fan
operation in
cooling

20

0

No extended fan
operation after the call
for cool ends

1

Fan operation is extended 90
seconds after the call for cool
ends.

Not used

21 thru 23

Outdoor
temperature
display (select
models)

24

0

No outdoor
temperature is
displayed

1

Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor Sensor
to operate

Not used

25 thru 29

Deadband

30

3

Heating and cooling
setpoints can be set
no closer than 3°F
(1.5°C)

4 thru 10

Heating and cooling setpoints
can be set no closer than the
chosen value:

4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)

a

Number 2 must be set to 1 to extend fan operation.