Operation, Operation sequence, Using daylight savings time feature – Honeywell CHRONOTHERM T8602D User Manual

Page 16: Displaying the outdoor temperature, P+i control, Equipment protection, Iv deluxe programmable thermostats, Auto, Auto none o or b, None

Advertising
background image

T8600D, T8601D AND T8602D CHRONOTHERM

®

IV DELUXE PROGRAMMABLE THERMOSTATS

68-0164—1

16

M10342

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Copy

Outdoor

HEATING

COOLING

PERCENT LOAD

TEMPERATURE

THERMOSTAT
HEAT SETPOINT

P+I CONTROL
POINT

PROPORTIONAL COOL
CONTROL POINT

THERMOSTAT
COOL SETPOINT

P+I CONTROL POINT

PROPORTIONAL HEAT
CONTROL POINT

M4414

100

50

0

50

100

Fig 13. Proportional temperature control versus P+I

temperature control.

Operation Sequence

The thermostat energizes specific terminals depending what
the Fan and System are set to. The LCD will display the time,
room temperature, system and fan selection. Symbols will be
displayed when the heating, cooling or fan is energized. See
Table 10 for specific information.

NOTE:

Not all the thermostat models have all the terminals
listed in the Energize column.

Table 10. Conventional System Sequence of Operation.

Using Daylight Savings Time Feature

This feature allows you to change in and out of Daylight
Savings Time with a key press. When the Daylight Time Key is
pressed in the fall, the time will go back one hour. In the
spring, the time will go ahead one hour and the display will
show DST. See Setting the Current Day and Time section for
initial setting instructions.

NOTE:

Pressing the Daylight Time Key more than once
within a five minute period will scroll you through
various time options (Example: one hour earlier or
later with or without DST). Pressing the Daylight
Time Key six times in a five minute period will return
you to your original settings.

Displaying the Outdoor Temperature

If your thermostat is equipped with an outdoor sensor, you
can check the temperature at the sensor by pressing

i

once.

OPERATION

P+I Control

The thermostat microprocessor based control requires that
the user understands temperature control and thermostat
performance. A conventional electromechanical or electronic
thermostat does not control temperature precisely at setpoint.
Typically, there is an offset (droop) in the control point as the
system load changes. This is a phenomenon that most people
in the industry know and accept. Many factors contribute to
offset including switch differential, thermal lag, overshoot,
cycle rates and system load.

The thermostat microprocessor simultaneously gathers,
compares and computes data. Using this data, it controls a
wide variety of functions. The special proprietary algorithm
(program) in the thermostat eliminates the factors causing
offset. This makes temperature control more accurate than
the conventional electromechanical or electronic thermostats.
The temperature control algorithm is called proportional plus
integral (P+I) control.

The thermostat sensor, located on the thermostat or remote,
senses the current space temperature. The proportional error
is calculated by comparing the sensed temperature to the
programmed setpoint. The deviation from the setpoint is the
proportional error.

The thermostat also determines integral error, which is a
deviation based on the length of error time. The sum of the
two errors is the (P+I) error. The cycle rate used to reach and
maintain the setpoint temperature is computed using the P+I.
The addition of the integral error is what differentiates the
thermostat from many other electronic and electromechanical
thermostats. See Fig. 13.

Equipment Protection

As part of the operational sequence, the thermostat
microprocessor also incorporates minimum off time for all
cooling stages. Using the minimum off time assures that rapid
cycling of equipment does not occur, which extends
equipment life. Minimum off times are set in the Installer
Setup.

Selection

Fan

System

Call

Energize

Display

Auto

Off

None

None

None

On

Off

None

G

Auto

Cool

None

O

None

Auto

Cool or Auto

Cooling O, G and Y

and

Auto

Heat

None

B

None

Auto

Heat or Auto

Heating B and W

a

Auto

Auto

None

O or B

b

None

a

When electric heat fan is selected, G is energized and fan
symbol is displayed.

b

Based on last piece of equipment called (cooling = O or
heating = B) and Installer Setup selection.

M10341

Time

Set Program