T8600D, T8601D AND T8602D CHRONOTHERM

®

IV DELUXE PROGRAMMABLE THERMOSTATS

68-0164—1

5

WIRES
THROUGH WALL

WALL

MOUNTING
HOLES

M15044

MOUNTING
SCREWS

WALL
ANCHORS
(2)

Fig. 3. Mounting the wallplate.

IMPORTANT

Use 18 gauge, color-coded thermostat cable for
proper wiring.

2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to prevent

drafts from affecting the thermostat.

Standard

Terminal

Designations

Alternate

Terminal

Designations

Typical Connection

Function

Terminal Type

B

Heating damper or changeover valve

Output

24V powered contact

C

B

a

, C, X1, X2

Common

Input

G

F

Fan relay

Output

24V powered contact

O

R

Cooling damper or changeover valve

Output

24V powered contact

OT, OT

Outdoor temperature sensor (C7089B)

Input

R

V

24V system or heating transformer

Input

RC

24V cooling transformer

Input

W

H1, R3

Heating relay

Output

24V powered contact

Y

C1, M

Compressor contactor

Output

24V powered contact

a

Some OEM models label the terminal for transformer common B.

M4826

FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).

FOR STRAIGHT
INSERTION STRIP
5/16 IN. (8 MM).

Fig. 4. Proper wiring technique.

Mounting Thermostat Wallplate

The thermostat mounts on the wallplate after they are
installed.

1. Engage tabs at the top of thermostat and wallplate. See

Fig. 5.

2. Press lower edge of case to latch.

NOTE:

To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; then remove the top.

Table 4. Terminal Designations and Descriptions.