Installation – Harman Stove Company XL User Manual

Page 13

Advertising
background image

Installation

Only For Qualified Installers

Making The Connection

The gas inlet is located on the bottom right side

of the fireplace. The inlet fitting is 1/2” male flare fitting

designed for 1/2” stainless flex pipe. This fitting can be

removed to provide 3/8” female pipe thread.

A separate gas shut-off valve and a 1/8” N.P.T.

plugged tapping should be installed immediately up-

stream of the connection to the appliance.

The ShadowLight XL Direct Vent Gas Heater must

be disconnected from the gas supply piping during any

pressure testing of that system at pressures in excess

of 1/2 psig (3.5 kPa).

The ShadowLight XL gas control valve must be

in the OFF position during any pressure testing of the

gas supply system at pressures equal to or less than

1/2 psig (3.5 kPa).

WARNING: To avoid pipe compounds from enter-

ing into the gas train, apply compounds only to male

pipe threads and do not apply compound to the first

two threads.

CAUTION: TEST ALL JOINTS FOR LEAKS BE-

FORE OPERATING.

Gas Pressure Requirements:

Correct gas pressure and the use of a properly

sized gas supply line are essential for the safe and ef-

ficient performance of this appliance. Make sure that

the plumber or gas supplier checks the gas supply line

and gas pressure at installation.

NOTE: Improper gas pressure can affect heater

performance, flame color, or cause pilot outage.

Natural Gas:

Maximum inlet pressure 7.0” w.c. (1.74 kPa)

Minimum inlet pressure 5.0” w.c. (1.25 kPa)

Gas manifold pressure 3.5” w.c. (0.87 kPa)

LP Gas:

Maximum inlet pressure 13” w.c. (3.24 kPa)

Minimum inlet pressure 11” w.c. (2.74 kPa)

Gas manifold pressure 10” w.c. (2.49 kPa)

DO NOT USE THIS HEATER IF ANY PART HAS

BEEN UNDER WATER, EXPOSED TO MOISTURE,

OR SHOWS SIGNS OF CORROSION. IMMEDIATELY

CALL A QUALlFlED SERVICE TECHNICIAN TO IN-

SPECT THE HEATER AND REPLACE ANY PART OF

THE CONTROL SYSTEM AND ANY GAS CONTROL

WHICH HAS BEEN UNDER WATER.

Gas Line

CONNECTING THE SHADOWLIGHT XL

FIREPLACE INSERT TO A GAS SUPPLY

Test Class

Note: Stove is built for propane. A conversion

must be done to accomodate natural gas.

Do not connect the venting to the flue of a

chimney that serves a separate solid-fuel

burning appliance.

13