Chimney cap components, Installation – Harman Stove Company XL User Manual

Page 19

Advertising
background image

Installation

Only For Qualified Installers

Use Only Approved Venting

This appliance has been tested and is listed for

installation with Simpson Duravent GS and Duraflex

AL venting components. The warranty will be voided,

and serious fire, health, or other safety hazards may

result from any of the following actions:

• Installation of any damaged Simpson Duravent

component.

• Unauthorized modification of the Simpson Du-

ravent System.

• Installation of any component part not manufac-

tured or approved by Simpson Duravent.

• Installation other than as instructed by Simpson

Duravent and the appliance manufacturer.

Consult your local building codes before begin-

ning the installation, and follow the manufacturer’s

instructions exactly. The Simpson Duravent venting

components listed below are approved for use with

the ShadowLight XL Direct Vent Gas Insert.

Flashing

Chimney Liner Termination

Kit. Includes flashing.

Stock # 923GK

High Wind Cap

Stock# 991

Chimney Cap Components

Duraflex AL - Flexible Aluminum Pipe Lengths

Size

Length

Stock #

3”

25’

2270

3”

35’

2280

3”

50’

2290

Typical Chimney

Tile Liner

Vent Pipe

Air Intake Pipe

Uncoil the three inch aluminum chimney liners on the

ground and measure to make sure the pipes are long

enough. Mark one of the liners at both ends with paint

and use it for the exhaust side connection. Once they

are in the chimney it allows easier identification of

intake and exhaust connections.

Flashing

Figure__

Air Intake

Vent

Minimum vertical vent pipe length is 10 Feet.

Maximum horizontal distance is 36”.

A bead of silicone goes

between the top of

the tile liner and the

flashing to seal the cap

to the chimney

19