Venting – Harman Stove Company P43 User Manual

Page 7

Advertising
background image

7

P43 Pellet Stove

venting

requirements for terminating the venting

WARNING: Venting terminals must not be recessed

into a wall or siding.

NOTE: Only approved pellet vent pipe, wall pass-

throughs, and fire stops should be used when venting

through combustible materials.

NOTE: Always take into consideration the effects

of the prevailing wind direction or other wind currents

that may cause flyash and/or smoke when placing the

termination of the vent.

in addition, the following must be observed:

A. The clearance above grade must be a minimum

of 18".

1

B. The clearance to a window or door that may be

opened must be a minimum of 48" to the side, 48" be-

low the window/door, and 1" above the window/door.

1

(

with outside air installed, 18” to the side or below)

C. A 1" clearance to a permanently closed win-

dow is recommended to prevent condensation on

the window.

D. The vertical clearance to a ventilated soffit located

above the terminal within a horizontal distance of 

feet (60 cm) from the center-line of the terminal must

be a minimum of 18".

E. The clearance to an unventilated soffit must be

a minimum of 1".

F. The clearance to an outside corner is 11" from

center of pipe.

G. The clearance to an inside corner is 1".

H. A vent must not be installed within 3 feet (90 cm)

above a gas meter/regulator assembly when measured

from the horizontal center-line of the regulator.

1

I. The clearance to service regulator vent outlet must

be a minimum of 6 feet.

1

J. The clearance to a non-mechanical air supply inlet

to the building or the combustion air inlet to any other

appliance must be a minimum of 48”.

1

K. The clearance to a mechanical air supply inlet

must be a minimum of 10 feet.

1

(

with outside air installed, 6 feet )

L. The clearance above a paved sidewalk or a paved

driveway located on public property must be a mini-

mum of 7 feet.

1,2

M. The clearance under a veranda, porch, deck or

balcony must be a minimum of 1 inches.

1,3

NOTE: The clearance to vegetation and other exte-

rior combustibles such as mulch is 36” as measured

from the center of the outlet or cap. This 36” radius

continues to grade or a minimum of 7 feet below the

outlet.

1

Certain Canadian and/or Local codes or regula-

tions may require different clearances.

2

A vent shall not terminate directly above a side-

walk or paved driveway which is located between two

single family dwellings and serves both dwellings.

3

Only permitted if veranda, porch, deck, or balcony

is fully open on a minimum of  sides beneath the

floor.

nOte: where passage through a wall, or partition

of combustible construction is desired, the

installation shall conform to can/cSa-b365. (if

in canada)

= Vent terminal

v