INSTALLATION

Diagram 7

VERTICAL

TERMINATIONS

1) Maintain the 1-1/4" clearances (air spaces)

to combustibles when passing through ceil-
ings, walls, roofs, enclosures, attic rafter,
or other nearby combustible surfaces. Do
not pack air spaces with insulation. Check
the "Venting Arrangement" section for the
maximum vertical rise of the venting system
and the maximum horizontal offset limita-
tions.

2) Set the gas appliance in its desired loca-

tion. Drop a plumb bob down from the
ceiling to the position of the appliance fl ue
exit, and mark the location where the vent
will penetrate the ceiling. Drill a small hole
at his point. Next, drop a plumb bob from
the roof to the hole previously drilled in
the ceiling, and mark the spot where the
vent will penetrate the roof. Determine if
ceiling joists, roof rafters or other framing
will obstruct the venting system. You may
wish to relocate the appliance or to offset,
as shown in diagram 8 to avoid cutting load
bearing members.

Diagram 4

7) Install the Backing Plate into the wall penetra-

tion heat shield and attach using 4 screws.
Dia. 4.

8) Connect all pipe sections to unit and install

into wall:

a) Measure pipe length required and cut to

length. Hint: use the cut end of the 6-5/8"
dia. outer pipe at the vent terminal end.

b) Push the pipe sections completely together,

the minimum pipe overlap is 1-1/4". Secure
all outer pipe joints by using at least two
screws. Locate the screws at the bottom of
the pipe so that the screw heads are hidden
on the fi nal installation. Apply sealant "Mill-
Pac" to inner pipe and high temp silicone
sealant or "Mill-Pac" to outer pipe on every
joint.

Diagram 5

c) Before connecting the vent pipe to the vent

termination, slide the black decorative wall
thimble cover over the vent pipe, then slide
the Wall Penetration Heat Shield (Part #
946-202) over the vent pipe. Dia. 3.

d) Slide the appliance and vent assembly

towards the wall carefully inserting the vent
pipe into the riser vent terminal assembly. It
is important that the vent pipe extends into
the Riser Vent Backing Plate a suffi cient
distance so as to result in a minimum pipe
overlap of 1-1/4 inches. Secure the con-
nection between the vent pipe and the vent
cap by attaching the two sheet metal strips
extending from the Riser Vent Backing Plate
into the outer wall of the vent pipe. Use
two aluminum screws provided to connect
the strips to the pipe section. Bend any
remaining portion of the sheet metal strip
back towards the vent cap and cut off any
excess, it will be concealed by the decora-
tive wall thimble cover. See diagram 5.

8) Slide the decorative wall thimble up to the

wall surface being careful not to scratch the
paint. See diagram 5.

9) Back outside: Apply sealant to the 4" inner

fl ue and slide the Riser Vent Front into the
Backing Plate and fasten with 8 screws.

IMPORTANT:

When connecting the pipe to the Riser
Vent, apply Mill-Pac to the inner pipe on
the Riser Vent Terminal, around the bead.
Ensure that the vent pipe is pushed past
the bead for a secure fi t.

10) Seal around the outer edge of the Riser

Vent Backing Plate.

Hint: Apply sealant to female end.