Honeywell Chronotherm IV T8611G User Manual

Page 10

Advertising
background image

69-0936—1

10

T8611G CHRONOTHERM

®

IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

Symptom

Possible Cause

Action

Cooling will not
come on.

No power to the thermostat.

Check for 24 Vac between R and C.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the
circuit breaker.

check if the system fuse is blown—replace the
fuse.

check if the power switch on the HVAC equipment
is in the Off position—set to the On position.

check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is
activated.

Wait up to five minutes for the system to respond.

Enter Installer Setup number 33. Reconfigure minimum off
time (if required).

System selection is not set to
Cool.

Set system selection to Cool.

Cool setpoint is above room
temperature.

Check cooling setpoint. Set cooling setpoint to desired
temperature.

Heating or cooling
come on
momentarily and
shut off

Heat or cool circuit is opening
up or becoming high
impedance.

Add resistor in parallel with load or install interface relay.

System on indicator
(flame=heat,
snowflake=cool) is
displayed, but no
warm or cool air is
coming from the
registers.

Heating or cooling equipment is
not operating.

Verify operation of heating or cooling equipment in self-test.

Outdoor
temperature
not displayed

a

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must
have OT terminals and a C7089B1000 installed.

Outdoor
temperature

Outdoor sensor is connected
incorrectly.

Refer to C7089B1000 installation instructions and check wiring
between the thermostat and sensor.

display is incorrect

a

Wrong sensor.

Replace sensor with C7089B1000 sensor.

a

Select models.

Troubleshooting

(Continued).