69-0936—1

5

T8611G CHRONOTHERM

®

IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

M10349

INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2
OF TABLE 3)

FACTORY SETTING
OR OTHER CHOICE
DISPLAY (COLUMN 3
OR 5 OF TABLE 3)

A combination of key presses are required to use the
Installer Setup feature.

To enter the Installer Setup, press and hold the
Information

i

key with the increase

and

decrease

keys until the first number is displayed.

All display segments appear for approximately three
seconds before the number is displayed.
See Fig. 9 and 10.

To advance to the next Installer Setup, press the
Time

key.

To change a setting, use the increase

or

decrease

key.

To scroll the Installer Setup numbers backwards,
press the Time

key.

To exit the Installer Setup, press Run Program.

Aux Ht

Heat

Auto

System

Fan

Off

Auto

Wake

Mon

Wait

In

Room

Outdoor

%Humid

Auto

Sav

AM

PM

Hold for

Cool

Repl Batt

On

Recovery

DST

Cool

TueWedThuFriSatSun

LeaveReturnSleep

M10345

Set Program

Set Day/Time

Start Time

Temporary Setting Enrg

Em Heat

Em Ht

Fig. 10. Display of Installer Setup

number and setting.

IMPORTANT

Only configurable numbers are shown on the device.
Example: If thermostat does not have a system key,
Installer Setup Number 12 will not be displayed.
Review Table 3 factory-settings and mark any
desired changes in the Actual Settings column.
When Installer Setup is complete, review the
settings to confirm that they match the system.

Table 3. Thermostat Installer Setup Options.

(Continued)

Fig. 9. Display of all the segments of the LCD.

Installer

Setup

Number

(Press

Time

key to

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

change)

Display

Description

Display

Description

Setting

Not used

1 thru 4

Heating cycle

5

6

Stage 2

3, 6 or 9 3—3 cph

6 (Not

used)

6—6 cph used for last stage of

heat pump systems

7

9

Emergency heat

3, 6

or 9

9—9 cph used for electric
heat

Not used

8 thru 11

System setting
adjustment

12

1

Manual changeover

0 or 2

0—Auto changeover
2—Fixed auto changeover

Adaptive
Intelligent
Recovery™
control

13

0

Adaptive Intelligent
Recovery™ control is
activated (system
starts early so setpoint
is reached by start of
program period)

1

Conventional recovery (system
starts recovery at programmed
time)

Degree
temperature
display

14

0

Temperature is
displayed in °F

1

Temperature is displayed in °C

Not used

15

Clock format

16

0

12-hour clock format

1

24-hour clock format

Not used

17 and 18

Extended fan
operation in
heating

19

0

No extended fan
operation after the
call for heat ends

1

Fan operation is extended
90 seconds after the call for
heat ends.