When the fryer is leveled in its final position, install the restraints provided with the unit to limit
its movement so that it does not depend on or transmit stress to the electrical conduit or
connection. Install the restraints in accordance with the provided instructions (see illustration
below). If the restraints are disconnected for service or other reasons, they must be reconnected
before the fryer is used.

DANGER

Single fryers may tip and cause personal injury if not secured in a stationary
position.

5. If the fryer is equipped with a power cord, plug the cord securely into a properly grounded outlet

of appropriate voltage for the specific fryer configuration.

If the fryer is not equipped with a power cord, connect a power cord appropriate for the voltage
rating of the fryer in accordance with the field connection diagrams that follow. Refer to the
table on the following page to determine the appropriate wire gauge.

DANGER

Copper wire suitable for at least 167°F (75°C) must be used for power connections.

MINIMUM SIZE

VOLTAGE PHASE

WIRE

SERVICE

AWG

(mm

2

)

AMPS

(PER LEG)

208 1 3 6 16 31
208 3 3 6 16 18
240 1 3 6 16 27
240 3 3 6 16 16
480 1 3 8 16 14
480 3 3 8 10 8