FieldServer Carrier DataPort FS-8700-86 User Manual

Page 13

Advertising
background image

FS-8700-86 Carrier DataPort

Page 13 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Column Title

Function

Legal Values

DA_Byte_Name*

If this parameter is defined then its value must be
the name of a Data Array. Instead of the driver
returning a static Field Status, it will extract the
value located at the given offset and use this
value as the Field Status.

The name of Data Array
defined

in the Data

Arrays section.

On_String

If the variable has a discrete state, use this
parameter to define the word that describes the
state when the variable’s value is 1.
OR
Use one of the keywords to tell the driver to send
the value of the associated array elements:
NUMERIC – a number
TIME - a time value formatted as hh:mm
STRING - a string of bytes
DOW – occupancy string
When using the string keyword the driver reads x
consecutive array elements and treats them as
ASCII character values in forming the response.
X is defined by the length parameter.

NUMERIC
TIME
STRING
DOW
Or any other Ascii string
which may not contain
spaces.

Off_String

If the variable has a discrete state, use this
parameter to define the word that describes the
state when the variable’s value is zero. If you
have used a keywords described above then
simply put a dash in this field.

An ASCII string which
may not contain spaces.

Length

Always set the length to 1 unless you use the key
word ‘STRING’ as the On_String parameter.

1

5.4.3.

Timing Parameters

Column Title

Function

Legal

Values

Scada_Hold_Timeout

Specifies time Server side waits before responding to Client
that node is offline on FieldServer Client side.

>1.0s

Advertising