Appendix B.4.

How to build a script file that tests a customer log.

The following brief notes are intended for configuration engineers who are expected to be familiar
with the FieldServer.

Take the hex log file and convert to ASCII using special chars (this is an option of the log file
converter)

Choose a response line from near the end of the log (most recent). Check the line is complete.

Place the line inside an INI file. Make the following changes

Replace [NP] with [FF]

Replace [SP] with a space

Replace [NULL] with a space.

Use the following files as a guide.

Client.csv

Data_Arrays

Data_Array_Name, Data_Format, Data_Array_Length
DA_D1_01,

Float,

500

Connections

Port ,

Parity, Baud, Data_Bits, Stop_Bits, Handshaking, Protocol,

Timeout,

Print_storage_locations

P1,

None, 9600, 8,

1,

None,

CarrierDP, 60s,

Yes

Nodes

Node_Name, Node, Protocol, Port
Node_A ,

1,

CarrierDP, P1

Map_Descriptors

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scan_Interval,
CMD_GP_01,

DA_D1_01,

0,

Rdbc,

Node_A,

202,

5.0s

Server.csv

Data_Arrays

Data_Array_Name, Data_Format, Data_Array_Length
TABLE_DISPLAY,

Float,

500

Connections

Port ,

Parity, Baud, Data_Bits, Stop_Bits, Handshaking, Protocol,

P1,

None,

1200, 8,

1,

None,

CarrierDP,

Nodes

Node_Name, Node, Protocol,
Node_A ,

1,

CarrierDP,

Advertising