Appendix B.4.

How to build a script file that tests a customer log.

The following brief notes are intended for configuration engineers who are expected to be familiar
with the FieldServer.

•

Take the hex log file and convert to ASCII using special chars (this is an option of the log file
converter)

•

Choose a response line from near the end of the log (most recent). Check the line is complete.

•

Place the line inside an INI file. Make the following changes

•

Replace [NP] with [FF]

•

Replace [SP] with a space

•

Replace [NULL] with a space.

•

Use the following files as a guide.

Client.csv

Data_Arrays

Data_Array_Name, Data_Format, Data_Array_Length
DA_D1_01,

Float,

500

Connections

Port ,

Parity, Baud, Data_Bits, Stop_Bits, Handshaking, Protocol,

Timeout,

Print_storage_locations

P1,

None, 9600, 8,

1,

None,

CarrierDP, 60s,

Yes

Nodes

Node_Name, Node, Protocol, Port
Node_A ,

1,

CarrierDP, P1

Map_Descriptors

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scan_Interval,
CMD_GP_01,

DA_D1_01,

0,

Rdbc,

Node_A,

202,

5.0s

Server.csv

Data_Arrays

Data_Array_Name, Data_Format, Data_Array_Length
TABLE_DISPLAY,

Float,

500

Connections

Port ,

Parity, Baud, Data_Bits, Stop_Bits, Handshaking, Protocol,

P1,

None,

1200, 8,

1,

None,

CarrierDP,

Nodes

Node_Name, Node, Protocol,
Node_A ,

1,

CarrierDP,