FS-8700-86 Carrier DataPort

Page 6 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

4.2.

Client Side Connections

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device is connected to the
FieldServer

P1-P8, ( R1, R2 with
converter)

1

Baud*

Specify baud rate.

600 , 1200, 2400, 9600
(Vendor limitation)

Parity*

Specify parity

None (Vendor limitation)

Data_Bits*

Specify data bits

8 (Vendor limitation)

Stop_Bits*

Specify stop bits.

1 (Vendor limitation)

Protocol

Specify protocol used

CarrierDP

Handshaking*

Specify hardware handshaking

None

Poll _Delay*

Time between internal polls

0-32000

seconds,

1

second

Timeout

2

Specifies the max amount of time the driver must
wait for a complete response.

If the Data Port table is long then increase the
timeout above the default until timeout errors
disappear.

2 seconds

Application

Refer to notes in Appendix B.3

Print_storage_locations

Start_Method*

If the parameter is not configured or set to 0
(default), the driver will identify the start of a
message as FORMFEED (0x0C) and the end as two
carriage returns (0x0D 0x0D)

When the parameter is set to 1, the first carriage
return (0x0D) will be considered the start of the
message (all characters before the first carriage
return will be ignored). and the end as two carriage
returns (0x0D 0x0D)

1,0

Example

// Client Side Connections

Connections
Port,

Baud, Parity,

Data_Bits,

Stop_Bits,

Protocol ,

Handshaking,

Poll_Delay

P8, 9600,

None,

8 ,

1 ,

CarrierDP,

None ,

0.100s

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.

2

See Appendix B.1 for additional information