FieldServer Carrier DataPort FS-8700-86 User Manual

Page 16

Advertising
background image

FS-8700-86 Carrier DataPort

Page 16 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Error Conditions

Force Conditions

Conditions

A

B

C

D

E

F

No Force

0

1

2

3

4

5

Fire

16

17

18

19

20

21

Safety

32

33

34

35

36

37

Service Tool

48

49

50

51

52

53

Supervisor

64

65

66

67

68

69

Monitor

80

81

82

83

84

85

Minimum-off

96

97

98

99

100

101

Control

112

113

114

115

116

117

BEST

128

129

130

131

132

133

Temp Override

144

145

146

147

148

149

Loadshed

160

161

162

163

164

165

Error Conditions:
A

no error

B

hardware or communications error

C

software error

D

low alarm limit exceeded (analog point),or point in alarm (discrete point)

E

high alarm limit exceeded

F

unconfigured point (VVT Gateway only)

Force Conditions:
No Force

Fire

forced by fire alarm equipment

Safety

forced by internal safety override

Service Tool

forced by CCN Service Tool

Supervisor

forced by local Building Supervisor

Monitor

forced by remote Building Supervisor

Minimum-off

forced by minimum off time requirement

Control

forced by System Software Option

BEST

forced by BEST program

Temp Override

forced by temperature override

Loadshed

forced by Loadshed System Software Option

Appendix A.2.

Field / Variable Names

A list of variable names vs. table names vs. equipment types is not provided in this manual. The
reasons for this are that they are not all available to us they can be configured in some devices using
software provided by the Carrier Corporation.

Consult the points list with the literature provided with each type of equipment from Carrier to obtain
variable names. Alternately use the software provided by Carrier to browse the network and
determine the table and variable names.

This driver may also be used to obtain a list of variable names for a given table. On the following
pages are sample Map Descriptors which may be included in the configuration to help obtain this
information. FieldServer recommends that if these Map Descriptors are used to obtain variable name
information, they should be removed from the final configuration as they will consume resource and
processing time.

Advertising