Installation, Installation clearances, Continued – FMI VCM-36Q User Manual

Page 11

Advertising
background image

www.fmiproducts.com

122275-01G

11

INSTALLATION cLEARANcES

WARNING: Maintain the

minimum clearances. If you

can, provide greater clearances

from floor, ceiling, and adjoin-

ing wall.

Carefully follow the instructions below. This

will ensure safe installation.
Minimum Wall and Ceiling Clearances

(see Figure 6)

A. Clearances from the side of the fireplace

cabinet to any combustible material and

wall should follow diagram in Figure 6.

Example: The face of a mantel, bookshelf,

etc. is made of combustible material and

protrudes 3

1

/

2

" from the wall. This com-

bustible material must be 4" from the side

of the fireplace cabinet (see Figure 6).

B. Clearances from the top of the firebox

opening to the ceiling should not be less

than 42".

C. When the firebox is installed directly on

carpeting, tile or other combustible mate-

rial, other than wood flooring, the firebox

should be installed on a metal or wood

panel extending the full width and depth

of the enclosure.

D. Clearances from the bottom of firebox to

the floor is 0".

These fireboxes can be installed as free-

standing units against a wall with approved

cabinet mantels that may be available from

your retailer or supplier, or as a built-in unit.

The clearances are the same for either instal-

lation method.

INsTAllATIoN

Continued

Mantel clearances for built-In

Installation

If placing custom mantel above built-in fire-

box, you must meet the minimum allowable

clearance between mantel shelf and top of

firebox opening shown in Figure 7. These are

the minimum allowable mantel clearances

for a safe installation. Use larger clearances

wherever possible to minimize the heating of

objects and materials placed on the mantel.

cAUTION: Do not allow the

vent-free gas log heater to touch

or extend beyond the fireplace

screen.

NOTICE: Surface temperatures

of adjacent walls and mantels

become hot during operation.

Walls and mantels above the

firebox may become hot to

the touch. If installed properly,

these temperatures meet the

requirement of the national

product standard. Follow all

minimum clearances shown in

this manual.

Figure 7 - Minimum Mantel Clearances

for Built-In Installation

Supplied

Firebox Hood

Must Be Used

at All Times

Wire-mesh

Screen

Firebox

Noncombustible

Material May

Project Off this

Surface above

the Firebox Hood

Mantel Shelf

Note: Any portion of the
mantel shelf must NOT
extend beyond this profile.

12" 16" 20"

1

1

/

2

"

6

3

/

4

"

12"

Note: All vertical
measurements are
from top of fireplace
hood opening to
bottom of mantel shelf.
These minimum
clearances replace any
other recommended
clearances supplied
with your ANSI Z21.11.2
approved gas logs.

Wall board or facing

material (above

firebox) may be of

combustible material,

including decorative

mantel ornaments or

other similar projec-

tions off of the facing

material.

Framing

Material

Figure 6 - Minimum Clearance for

Combustible to Wall

*Minimum 16" from Side Wall

Example

*

Advertising
This manual is related to the following products: