Air for combustion and ventilation – FMI VCM-36Q User Manual

Page 9

Advertising
background image

www.fmiproducts.com

122275-01G

9

AIr For CoMBUsTIoN ANd VeNTIlATIoN

Continued

1. Determine the volume of the space (length

x width x height).

Length x Width x Height =__________cu. ft.

(volume of space)

Example: Space size 22 ft. (length) x 18 ft.

(width) x 8 ft. (ceiling height) = 3,168 cu. ft.

(volume of space)

If additional ventilation to adjoining room

is supplied with grills or openings, add the

volume of these rooms to the total volume

of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example: 3,168 cu. ft. (volume of space) x 20 =

63,360 (maximum Btu/Hr space can support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free fireplace _________ Btu/Hr

Gas water heater* _________ Btu/Hr

Gas furnace

_________ Btu/Hr

Vented gas heater _________ Btu/Hr

Gas fireplace logs _________ Btu/Hr

Other gas appliances* + _________ Btu/Hr

Total

= _________ Btu/Hr

* Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the

outdoors and vents to the outdoors.

Example:

Gas water heater

_________ Btu/Hr

Vent-free fireplace + _________ Btu/Hr

Total

= _________ Btu/Hr

4. Compare the maximum Btu/Hr the space

can support with the actual amount of Btu/Hr

used.

_______ Btu/Hr (maximum the space can

support)

_______ Btu/Hr (actual amount of Btu/Hr

used)

Example: 63,360 Btu/Hr (maximum the

space can support)

79,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the example is a confined space

because the actual Btu/Hr used is more than the

maximum Btu/Hr the space can support. You

must provide additional fresh air. Your options

are as follows:

A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an

unconfined space, remove door to adjoining

room or add ventilation grills between rooms.

See Ventilation Air From Inside Building.

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 10.

C. Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined.

Figure 4 - Ventilation Air from Inside

Building

If the actual Btu/Hr used is less than the

maximum Btu/Hr the space can support, the

space is an unconfined space. You will need

no additional fresh air ventilation.

WARNING: If the area in which

the heater may be operated does

not meet the required volume for

indoor combustion air, combus-

tion and ventilation air shall be

provided by one of the methods

described in the National Fuel

Gas Code, ANSI Z223.1/NFPA 54,

the International Fuel Gas Code,

or applicable local codes.

vENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining

unconfined space. When ventilating to an

adjoining unconfined space, you must provide

two permanent openings: one within 12" of the

ceiling and one within 12" of the floor on the

wall connecting the two spaces (see options

1 and 2, Figure 4). You can also remove door

into adjoining room (see option 3, Figure 4).

Follow the National Fuel Gas Code, ANSI

Z223.1/NFPA 54, Air for Combustion and

Ventilation for required size of ventilation

grills or ducts.

40,000

39,000

79,000

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining

Room,

Option 1

12"

12"

Advertising
This manual is related to the following products: