Installation instructions, Site requirements, 5 extra flue lengths – Stovax PR0919 User Manual

Page 13: Gas supply, Ventilation

Advertising
background image

13

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1C

AR1673

2.3 TOP FLUE VERTICAL kIT (8524/8524AN)

Vertical from the top of the appliance (See Diagram 1C).

A minimum vertical rise 3m (9’10") to a maximum 10m

(32’10"). The basic kit comprises:

2 x 1m lengths

1 x 1m terminal length

1 x 52mm restrictor

1 x 47mm restrictor

1 x 60mm restrictor

Extra lengths may be added from the list below.

2.4 TOP FLUE VERTICAL OFFSET kIT

(8530/8530AN)

Used with kit 8524. A minimum rise of 500mm (19

1/2

) is

required to the first bend. See Diagram 1C.

2.5 EXTRA FLUE LENGTHS

All flue components are 150mm diameter (6")

NOMINAL

ACTUAL

STAINLESS

ANTHRACITE

LENGTH

LENGTH

FINISH

FINISH

200mm

140mm

8527

8527AN

500mm

440mm

8528

8528AN

1000mm

940mm

8529

8529AN

40° Bend

N/A

8507

8507AN

90° Bend

N/A

8508

8508AN

NOTE: Carefully consider:
a)

Terminal positions

b)

Flue supports

c)

Weatherproofing

d)

Fire precautions

For all the above options, you must conform to local and

national codes of practice .

3. GAS SUPPLY

THIS APPLIANCE IS INTENDED FOR USE ON A GAS

INSTALLATION WITH A GOVERNED METER.

3.1 Before installation, ensure that the local distribution

conditions (identification of the type of gas and pressure)

and the adjustment of the appliance are compatible.

3.2 Ensure the gas supply delivers the required amount of gas

and is in accordance with the rules in force.

3.3 You can use soft copper tubing on the installation and soft

soldered joints outside the appliance and below the fire.

3.4 A factory fitted isolation device is part of the inlet

connection; no further isolation device is required.

3.5 All supply gas pipes must be purged of any debris that may

have entered prior to connection to the appliance.

3.6 The gas supply enters through the silicone panel located on

the LEFT-HAND side of the outer box:

• Slit with a sharp knife prior to pass the supply pipe

through.

3.7 The gas supply must be installed in a way that does not

restrict the removal of the appliance for servicing and

inspection.

4. VENTILATION

4.1 This appliance requires no additional ventilation.