Unit start-up checklist – Greenheck Fan Energy Recovery Ventilator with Heat Pump 473501 User Manual

Page 14

Advertising
background image

14

Model ERCH-HP Energy Recovery Unit

Line Voltage. Check at unit disconnect.

L1-L2

Volts

L2-L3

Volts

L1-L3

Volts

Motor Amp Draw

Supply Motor Amps

L1

Amps

L2

Amps

L3

Amps

Exhaust Motor Amps

L1

Amps

L2

Amps

L3

Amps

Fan RPM

Supply Fan RPM

Exhaust Fan RPM

Correct fan rotation direction?

Supply Fan

Yes / No

Exhaust Fan

Yes / No

Energy Wheel Motor

L1

Amps

L2

Amps

L3

Amps

Compressors

Compressor 1

L1

Amps

L2

Amps

L3

Amps

Crankcase Heater

Amps

Compressor 2

L1

Amps

L2

Amps

L3

Amps

Crankcase Heater

Amps

Condensing Fans

Condensing Fan 1

L1

Amps

L2

Amps

L3

Amps

Condensing Fan 2

L1

Amps

L2

Amps

L3

Amps

Condensing Fan 3

L1

Amps

L2

Amps

L3

Amps

Outdoor Air Temperature

Deg F

Return Air Temperature

Deg F

Outdoor Air Relative Humidity

% RH

Return Air Relative Humidity

% RH

Superheat

Deg F

Should be between 8º and 12ºF

Subcooling

Deg F

Should be between 12º and 17ºF

Discharge Pressure

PSIG

Should be between 200 and 280 PSIG for R22 or 300 and 500 PSIG for R410a

Suction Line Pressure

PSIG

Should be between 60 and 80 PSIG for R22 or 100 and 135 PSIG for R410a

Liquid Line Temp

Deg F

Suction Line Temp

Deg F

Moisture Indicating Sight Glass

Liquid Visible? Yes / No

Color of Center Dot: Green / Yellow

Hot Gas Bypass Operational

Yes / No

Unit Start-Up Checklist