Unit protection module (upm) fault indications – Greenheck Fan Energy Recovery Ventilator with Heat Pump 473501 User Manual

Page 27

Advertising
background image

27

Model ERCH-HP Energy Recovery Unit

Unit Protection Module (UPM)

Fault Indications

Each unit includes one Unit Protection Module (UPM)
printed circuit board and each UPM has two LED
indictor lights.

LED

Color

LED Fault Indication

Green Power LED indicates 18-30 VAC present at

the board

Red

Dual or

Single

Compressor

# of

blinks

Status

Dual

Compressor

1

High pressure lockout

Compressor 1

2

Low pressure lockout

Compressor 1

3

High pressure lockout

Compressor 2

4

Low pressure lockout

Compressor 2

5

Freeze sensor lockout

(optional item)

6

Condensate overflow

in coil drain pan

(optional item)

7

Brownout AC voltage

to R and C terminal

below 18 VAC

Single

Compressor

1

High pressure lockout

2

Low pressure lockout

3

Freeze sensor lockout

(optional item)

4

Condensate overflow

in coil drain pan

(optional item)

5

Brownout AC voltage

to R and C terminals

below 18 VAC

Intelligent Reset
If a fault condition is initiated, the five minute delay
on break time period and the random start timer is
initiated and the unit will restart after these delays
expire. During this period the fault LED will indicate
the cause of the fault. If the fault condition occurs 2 or
4 times (depending on 2 or 4 setting for Lockout dip
switch) before 60 minutes, the unit will go into a hard
lockout and requires a manual lockout reset. A single
condensate overflow fault will cause the unit to go into
a hard lockout immediately, and will require a manual
lockout reset.

Lockout Reset
A hard lockout can be reset by turning the unit
thermostat off and then back on when the “RESET” dip
switch is set to “Y” or by shutting off unit power at the
circuit breaker when the “RESET” dip switch is set to
“R”.
Your UPM board will come
from the factory with the
following default settings:

Default Settings

Freeze

NO

Temp

35°

Lockout

2

Reset

T

Alarm

CONT

Test

NO

Hot/Dry Alarm

HOT