Model ERCH-HP Energy Recovery Unit

Refrigeration System Schematic

Typical Operating Conditions

Location

Refrigerant State

Temperature

Pressure

Superheat/Subcool

Cooling

Mode /

Refrigerant

Properties

Before water-to-refrigerant

heat exchanger

Hot Vapor

150°F

330 PSIG

50°F Superheat

After water-to-refrigerant

heat exchanger

Warm Liquid

85°F

330 PSIG

15°F Subcool

After Thermostatic

Expansion Valve

Saturated Liquid-

Vapor mix

-45°F

144 PSIG

After Airside Coil

Cold Vapor

55°F

145 PSIG

10°F Superheat

Water entering the coaxial heat exchanger is warmed by the heat it absorbs from the refrigerant and leaves about

10°F warmer.

Location

Refrigerant State

Temperature

Pressure

Superheat/Subcool

Heating

Mode /

Refrigerant

Properties

Before Airside Coil

Hot Vapor

130°F

250 PSIG

50°F Superheat

After Airside Coil

Warm Liquid

65°F

250 PSIG

15°F Subcool

After Thermostatic

Expansion Valve

Saturated Liquid-

Vapor mix

-35°F

120 PSIG

After water-to-refrigerant

heat exchanger

Cold Vapor

45°F

120 PSIG

10°F Superheat

Water entering the coaxial heat exchanger is cooled because of the heat being absorbed by the refrigerant and

leaves about 6

°F warmer.