Installation – Greenheck Fan Energy Recovery Ventilator with Heat Pump 473501 User Manual

Page 7

Advertising
background image

7

Model ERCH-HP Energy Recovery Unit

Installation

Model

Overall Exterior Dimensions

Width

(including Lifting Lugs)

Overall Width

(with Exhaust Hood)

Overall Length

(with Outdoor Air Hood)

ERCH-HP 20

59.5

75

116

ERCH-HP 45

69.5

86

122

ERCH-HP 55

79.5

101

134

ERCH-HP 90

99.5

123

147

All dimensions shown are in inches.

Unit Size

U

V

Approximate

Weight (pounds)

ERCH-HP 20

46

37

2150

ERCH-HP 45

54

39

3500

ERCH-HP 55

65

47

4450

ERCH-HP 90

85

49

5300

All dimensions are in inches. Unit weights assume rooftop

configuration with weatherhoods, filters, outdoor air damper,

six row DX coil, integral condensing section and an indirect

gas-fired furnace.

Supply

Discharge

Exhaust

Intake

U

V

1/2 inch

1/2 inch

1/2 inch

Position the unit roof opening such that the supply
discharge and exhaust inlet of the unit will line up with
the corresponding ductwork. Be sure to allow for the
recommended service clearances when positioning
opening (see Service Clearances). Do not face the
outdoor air intake of the unit into prevailing wind and
keep the intake away from any other exhaust fans.
Likewise, position the exhaust discharge opening away
from outdoor air intakes of any other equipment.

Unit Weights and Recommended Roof Opening

Dimensional Data