INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1. FLUE AND CHIMNEY REQUIREMENTS

NOTE: This appliance can only be installed in conjunction

with the flue supplied.

1.1 The flue must be sited in accordance with BS5440: Part 1

(latest editon). See diagram 1.

1.2 Any terminal which is less than 2 metres above any access

(level ground, balcony or above a flat roof to which people

have access), is to be fitted with the guard.

1.3 All vertical and horizontal flues must be securely fixed and

fire precautions followed in accordance with local and

national codes of practice.

1.4 A restrictor may be required. Refer to Technical

Specifications on previous page.

1.1 TIMBER FRAMED BUILDINGS

1.5

It will be necessary to provide additional clearance when

the fire passes through a wall containing any combustible

materials so as to prevent a fire hazard.

1.6 The hole through which the flue will pass, must have a steel

sleeve which is positioned so that an air gap of at least

25mm is maintained between the outer surface of the flue,

and any part of the sleeve.

1.7 For further guidance on the installation of gas appliances in

timber framed buildings, contact your local buildings control

authority.
NOTE: ATTENTION MUST BE GIVEN TO ALLOWING

ADEQUATE CLEARANCE AT THE SIDES AND REAR OF

THE STOVE, TO PROVIDE ACCESS FOR SERVICING.