Installing duct collars – Greenheck Fan 452413 User Manual

Page 16

Advertising
background image

16

Canopy Hood

®

HOOD SECTION VIEW

DEFLECTOR TO BE PLACED CENTERED
UNDER THE SUPPLY DUCT COLLAR

SUPPLY
FIRE DAMPER

INTERNAL

SUPPLY

CHAMBER

HOOD

INSULATED
SUPPLY PLENUM

EXHAUST

CAPTURE

SUPPLY LOCATION DETAIL FOR

AIR CURTAIN AND COMBINATION

Hanger Bracket

Exhaust Plenum

Duct Cut Out Area

Duct Cut Out Area

Supply Plenum

Hood Length

Hood Width

Front of Hood

Exhaust Plenum

8.00

8.00

8.00

3.00

3.00

16.00

14.00

8.00

1.00

12.00

A CONTINUOUS LIQUID TIGHT WELD TO HOOD.

EXHAUST DUCT CONNECTION IS TO BE

CONNECTION

EXHAUST DUCT

FRONT OF HOOD

HANGER BRACKET

EXHAUST PLENUM

EXHAUST PLENUM

SUPPLY PLENUM

DUCT CUT OUT AREA

LABELED SUB-ASSEMBLY FOR EXHAUST HOOD WITHOUT EXHAUST DAMPER PART NO. DC.

2. U.L. LISTED HOOD ASSEMBLY TO BE USED ONLY WITH GREENHECK FAN CORP.

CENTER OF HOOD LENGTH TO CENTER OF DUCT CONNECTION.

NOTES: 1. EXHAUST DUCT CONNECTION TO BE LOCATED WITH IN 48" FROM

1" TO 2" TACKS OR SHEET METAL SCREWS AT 3" TO

6" SPACING TO HOOD.

SUPPLY DUCT CONNECTION TO BE TACK WELDED WITH

CONNECTION

SUPPLY DUCT

DUCT CUT OUT AREA

Hanger Bracket

Exhaust Plenum

Duct Cut Out Area

Duct Cut Out Area

Supply Plenum

Hood Length

Hood Width

Front of Hood

Exhaust Plenum

8.00

8.00

8.00

3.00

3.00

16.00

14.00

8.00

1.00

12.00

Back View of the Hood

Fig 25

Fig. 26

Fig. 27

Fig. 28

Note: UL listed hood
assembly to be used
only with Greenheck
Fan Corp. labeled
subassembly for
exhaust hood without
exhaust damper part
Number DC.

Hood Top

1. The exhaust duct

connection needs to
be located within 48 in.
(121.92 cm) from the
center of the hood
length to the center of
the duct connection.
(see Fig. 24, back view
Fig. 25)

2. The exhaust duct

connection is to be
a continuous liquid-
tight weld. Weld with
a non-ferrous filler
wire, such as silicon
bronze or stainless
steel filler wire. Protect
all stainless steel areas
from weld splatter.

3. The supply duct

connection is tack-
welded at 1 to 2 in.
(2.54 to 5.08 cm)
intervals, or sheet metal
screws at 3 to 6 in.
(7.62 cm to 15.24 cm)
spacing to the hood.
(Fig. 26)

4. The deflector is

centered under the
supply duct collar.
(Fig. 28)

5. For hoods that are

insulated, the edges of
the insulation need to
be taped after the hole
is cut, (the insulation
tape is to be provided
by others).

6. On combination hoods,

make sure the fire
damper is located over
the internal supply
chamber. (Fig. 29)

Top View of the Hood

Fig. 24

Installing Duct Collars