Installing the supply duct collar to the plenum, Fig. 10 fig. 9, Fig. 11 – Greenheck Fan 452413 User Manual

Page 9: Plenum

Advertising
background image

9

Canopy Hood

®

ATTACHED AIR CURTAIN CANOPY STYLE HOOD

ATTACHED AIR CURTAIN CANOPY STYLE HOOD

BACKSUPPLY BACKSHELF HOOD

BACKSUPPLY CANOPY STYLE HOOD

BACKSUPPLY CANOPY STYLE HOOD

VARIABLE SUPPLY PLENUM CANOPY STYLE HOOD

ATTACHED AIR CURTAIN CANOPY STYLE HOOD

ATTACHED AIR CURTAIN CANOPY STYLE HOOD

BACKSUPPLY BACKSHELF HOOD

BACKSUPPLY CANOPY STYLE HOOD

BACKSUPPLY CANOPY STYLE HOOD

VARIABLE SUPPLY PLENUM CANOPY STYLE HOOD

ASP - Air Curtain Supply Plenum

HSP or VSP - Variable Supply

Plenum

1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by others) into

hanger brackets on the supply plenum top. Raise and hang
the external supply plenum from adequate roof or ceiling
supports.

2. The external supply plenum should be resting lightly against

the hood. The hood is used to position the plenum only, it is
not

intended to support the plenum. All hanger brackets must

be used and the plenum must be properly supported while
lifting to prevent damage or distortion. The supply plenum
must be hung level to operate properly.

(Optional fastening of supply plenum to hood. See directions
below).

3. It is recommended that caulk be applied at the mating seams

and surfaces of the plenum, the hood, and the wall. If the
supply plenum is next to a wall, you will also need to caulk
around the surface next to the wall. Caulk the joints with NSF
Approved silicone caulk (GE SCS1009, or its equivalent). The
caulk is not provided.

Installing the Supply Duct Collar to the Plenum

1. Place the duct collar(s) over the opening, fastening with tack-

welds at 1 to 2 in. (2.54 to 5.08 cm) intervals, or sheet metal
screws at 3 to 6 in. (7.62 to 15.24 cm) intervals.

External Supply Plenum Weights, Dimensions, and Supply Rates

Fig. 10

Fig. 9

Using the UL Listed Fastener Provided

1. Drill a 9/32 in. hole for the 1/4 in. bolt from the inside of the supply plenum to

inside the hood. Fasteners are to be located max. 6 in. (15.24 cm) from the
end of the hood with max. spacing between bolts 36 in. (91.44 cm)

DO NOT

iNcluDe

uTiliTy

cabiNeTs

Or

fillers

wheN

figuriNg

bOlT

placemeNT

.

DO NOT

bOlT

The

supply

pleNum

TO

a

fire

/

uTiliTy

cabiNeT

.

2. Push bolt through hole, attach the washer and nut.

3. Hand tighten, then use a wrench until fully tightened. Caulk around bolts

from inside of hood as necessary.

HOLE SIZE 9/32 in.

Installation instructions for the AC3 fastener:

1) Create a 9/32 in. hole for ºî bolt.

2) Install bolt through hole.

3) Install appropriate washer (1/4 in.)
4) Install nut

7) Hand tighten, then use a wrench until tightened.

HOOD

1/4 - 20 UNC - 2A
SS BOLT

1/4 IN. SS NUT

SS FLAT WASHER

Fig. 11

External Supply

Plenum Type

Weight

Width

Height

Length per

section

Recommended

Supply Rate

(lbs/ft)

(kg/ft)

(in)

(mm)

(in)

(mm)

(ft)

(m)

Back Supply

35.0

15.878

6

152.4

Variable

Variable

3 to 16

.91 to

4.88

145 cfm/ft

(246.36 m

3

/hr)

Air Curtain Supply
• 14 inch

9.5

4.31

14

355.6

10

254

3 to 16

.91 to

4.88

110 cfm/ft

(186.89 m

3

/hr)

Air Curtain Supply
• 24 inch

12.5

5.67

24

609.6

10

254

3 to 16

.91 to

4.88

145 cfm/ft

(246.36 m

3

/hr)

Variable Supply

16.0

7.26

12

304.8

18

457.20

3 to 16

.91 to

4.88

curtain

0-80 cfm/ft

(0-135.92 m

3

/hr)

face

80-160 cfm/ft

(135.92 -271.84 m

3

/hr)

Horizontal Supply

14.0

6.35

12

304.8

18

457.20

3 to 16

.91 to

4.88

150 cfm/ft

(254.85 m

3

/hr)