Greenheck Fan 452413 User Manual

Page 22

Advertising
background image

22

Canopy Hood

®

Rotation Vane
Anemometer

2 in.

Fig. 35

Fig. 36

Cartridge Filter Size

Imperial

Conversion Factor

Metric

Conversion Factor

16 in. (400 mm) high with 4 in. (100 mm) high inlet

1.63 1/

ft

3

5.35 1/

m

3

20 in. (500 mm) high with 4 in. (100 mm) high inlet

2.15 1/

ft

3

7.05 1/

m

3

16 in. (400 mm) high with 7 in. (120 mm) high inlet

1.24 1/

ft

3

4.07 1/

m

3

20 in. (500 mm) high with 7 in. (120 mm) high inlet

1.58 1/

ft

3

5.18 1/

m

3

Filter Readings (fpm)

470

440

425

482

430

453

455

431

441

399

439

465

Filter Readings (m/hr)

8595

8047

7772

8815

7864

8284

8321

7882

8065

7297

8028

8504

High Velocity Cartridge Filters

A. Exhaust

With all the filters in place, determine the total hood exhaust
volume with a rotating vane anemometer as follows:

1. All cooking equipment should be on. If the hood has

internal short circuit make-up air, it should be turned off.

2. Measuring Velocities

• Velocity measurement should be taken at three locations per filter.

These must be over the inlet opening as shown in Fig. 35.

• Measure the velocity of each location. A digital 2.75 in. (70 mm)

rotating vane anemometer or its equivalent is suggested. The center
of the anemometer should be held 2 in. (50 mm) from the face of
the filters as in Fig. 31. It is helpful to make brackets to keep the
anemometer at the 2 in. (50 mm) distance and parallel to the filter.
Both squareness and distance are important for accuracy.

3. Calculate the average slot velocity.
4. Calculate the CFM per linear foot by dividing the average velocity by a

conversion factor listed in the following table.

5. Calculate the hood’s exhaust volume by multiplying the CFM per linear

foot by the length of hood.

1/4 Width

1/4 Width

1/2 Width

1/2 Height

Inlet Height

Filter Height

Example:
Measure the slot velocities in fpm for a 9 ft. (2.74 m) hood with four 20 x 20 in. (500 x 500 mm)
filters with standard opening, three readings per filter.

Average slot velocity

=

Sum of Velocity Readings
Number of Readings

(Imperial)

=

5330

12

= 444.2 fpm

(Metric)

=

97474

12

= 8123 m/hr

CFM per linear foot

=

Average Slot Velocity
Conversion Factor

=

444.2 fpm

2.15

= 206.6 cfm/linear foot

=

8123 m/hr

7.05

= 1152 m

3

/hr

Hood exhaust volume

=

CFM/linear foot (m

3

/hr / m)

x

Hood Length

=

206.6

x

9 ft.

= 1859.4 cfm

=

1152

x

2.74 m

= 3156 m

3

/hr