Roof downblast - belt drive size- : gb • h-gb – Greenheck Fan Centrifugal Roof Downblast Exhaust Fans GB User Manual

Page 26

Advertising
background image

DO

N

O

T

S

E

L

E

C

T

T

O

T

H

E

L

E

F

T

O

F

T

H

IS

S

Y

S

T

E

M

C

U

R

V

E

Static Pr

essur

e (in. wg)

Static Pr

essur

e (Pa)

Volume (cfm)

3

Volume (m /hr )

RPM

(Belt)

RPM

(Direct)

RPM

(Vari-Green)

HP

Density 0.075 lb/ft

3

Density 1.2 kg/m

3

2200

Motor HP

Fan

RPM

Static Pressure in Inches wg

Belt

Direct

.5

.75

1

1.25

1.5

1.75

2

2.25

2.5

2.75

141HP

143HP

1/4

VG-

3/4

1020

CFM

488

BHP

0.08

Sones

6.3

B-1/4

1140

CFM

645

413

BHP

0.11

0.11

Sones

7.7

7.6

1320

CFM

837

700

486

BHP

0.17

0.18

0.17

Sones

10.3

9.8

9.9

1500

CFM

1009

903

774

592

BHP

0.24

0.26

0.26

0.25

Sones

13.1

12.3

12.2

12.4

1/3

1655

CFM

1151

1064

959

833

668

BHP

0.32

0.34

0.35

0.35

0.34

Sones

15.0

14.1

13.3

13.1

13.6

1/2

A-1/2

1725

CFM

1213

1132

1035

932

784

588

BHP

0.36

0.38

0.39

0.39

0.39

0.37

Sones

16.2

15.4

14.7

14.2

14.3

14.9

1812

CFM

1289

1213

1127

1030

911

763

545

BHP

0.41

0.43

0.45

0.46

0.45

0.45

0.41

Sones

17.8

17.2

16.6

15.8

15.6

15.9

16.6

1900

CFM

1366

1294

1218

1127

1033

901

753

BHP

0.47

0.49

0.51

0.53

0.53

0.52

0.51

Sones

19.0

18.4

18.0

17.4

16.8

16.7

17.0

3/4

2050

CFM

1495

1430

1361

1285

1200

1113

991

857

672

BHP

0.58

0.61

0.63

0.65

0.66

0.66

0.66

0.65

0.61

Sones

21.0

20.0

19.8

19.3

18.8

18.6

18.3

18.3

18.6

2170

CFM

1598

1536

1472

1407

1328

1248

1163

1045

919

757

BHP

0.68

0.71

0.73

0.76

0.77

0.78

0.79

0.78

0.77

0.74

Sones

22.0

22.0

21.0

21.0

21.0

21.0

21.0

20.0

19.7

19.8

2200

CFM

1623

1562

1500

1436

1360

1281

1200

1088

968

834

BHP

0.71

0.74

0.76

0.78

0.80

0.82

0.82

0.81

0.80

0.79

Sones

23.0

22.0

22.0

22.0

21.0

21.0

21.0

21.0

20.0

20.0

26

Roof Downblast - Belt Drive
Size- : GB • H-GB

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.

Roof Downblast - Exhaust
Belt & Direct Drive
GB-141HP • G-143HP

Damper Size = 16 x 16
Roof Opening = 18½ x 18½

(470 x 470)

Shroud Thickness = 0.051

(1.3)

Motor Cover Thickness = 0.040

(1.0)

Curb Cap Thickness = 0.064

(1.6)

^Approximate Unit Weight G/GB = 75/83 lbs.

(34/38 kg)

All dimensions in inches (millimeters). *May be greater depending on
motor. ^Weight shown is largest cataloged Open Drip-Proof motor.

MAXIMUM BHP AT A GIVEN RPM = (RPM/2351)

3

MAXIMUM RPM - GB-141HP=2200, G-143HP=2200

TIP SPEED (ft/min) = RPM x 3.829

MAXIMUM MOTOR FRAME SIZE = 145T

1

3

4

(44)

4

(102)

*23

3

4

(603)

22

(559)

28

3

8

(721)

B-1140

-

RPM

A-1725

-

RPM

VG-2200

-

RPM

Direct Drive RPM

Advertising