Roof downblast - exhaust belt drive gb-240 – Greenheck Fan Centrifugal Roof Downblast Exhaust Fans GB User Manual

Page 35

Advertising
background image

35

Roof Downblast - Exhaust
Belt Drive
GB-240

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects
of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: free inlet hemispherical sone levels.

1

3

4

(44)

Damper Size = 24 x 24

(610 x 610)

Roof Opening = 26½ x 26½

(673 x 673)

Shroud Thickness = 0.064

(1.6)

Motor Cover Thickness = 0.040

(1.0)

Curb Cap Thickness = 0.064

(1.6)

^Approximate Unit Weight = 165 lbs.

(75 kg)

All dimensions in inches (millimeters). *May be greater depending on
motor. ^Weight shown is largest cataloged Open Drip-Proof motor.

DO

N

O

T

S

E

L

E

C

T

T

O

T

H

E

L

E

F

T

O

F

T

H

IS

S

Y

S

T

E

M

C

U

R

V

E

Static Pr

essur

e (in. wg)

Static Pr

essur

e (Pa)

Volume (cfm x 1000)

3

Volume (m /hr x 1000)

RPM

(Belt)

HP

Density 0.075 lb/ft

3

Density 1.2 kg/m

3

Motor

HP

Fan

RPM

Static Pressure in Inches wg

0

0.125

0.25

0.375

0.5

0.625

0.75

1

1.25

1.5

240

1/4

425

CFM

3902

3422

2691

BHP

0.19

0.21

0.20

Sones

5.9

5.9

4.7

460

CFM

4223

3785

3188

2036

BHP

0.24

0.26

0.27

0.22

Sones

6.7

6.6

5.7

4.2

1/3

505

CFM

4637

4242

3761

3060

BHP

0.32

0.35

0.35

0.34

Sones

7.8

7.5

6.9

6.1

1/2

585

CFM

5371

5031

4666

4195

3562

2112

BHP

0.50

0.53

0.54

0.55

0.53

0.41

Sones

10.3

9.7

9.1

8.8

8.2

7.2

3/4

623

CFM

5720

5400

5069

4660

4131

3428

BHP

0.60

0.64

0.65

0.66

0.65

0.61

Sones

11.7

11.0

10.4

10.0

9.6

9.1

660

CFM

6060

5757

5449

5094

4636

4073

3217

BHP

0.71

0.75

0.78

0.79

0.78

0.76

0.69

Sones

13.1

12.4

11.8

11.3

11.0

10.6

10.4

1

730

CFM

6702

6428

6158

5861

5507

5077

4568

BHP

0.96

1.01

1.05

1.05

1.06

1.06

1.03

Sones

15.8

15.0

14.3

13.8

13.4

13.1

12.9

1

1

2

778

CFM

7143

6886

6632

6363

6058

5700

5266

4145

BHP

1.16

1.21

1.26

1.27

1.28

1.29

1.28

1.18

Sones

17.7

16.6

15.9

15.4

15.0

14.7

14.4

13.2

825

CFM

7575

7332

7092

6844

6574

6261

5901

5002

BHP

1.39

1.44

1.49

1.51

1.52

1.54

1.53

1.48

Sones

19.7

18.6

17.7

17.2

16.8

16.4

16.2

14.8

2

870

CFM

7988

7757

7529

7300

7055

6775

6457

5680

7757

BHP

1.63

1.68

1.73

1.77

1.78

1.80

1.80

1.77

1.68

Sones

22

21

19.6

19.1

18.7

18.3

17.9

16.9

21

910

CFM

8355

8135

7916

7700

7467

7215

6933

6240

5388

3707

BHP

1.86

1.92

1.97

2.02

2.03

2.05

2.06

2.05

1.97

1.66

Sones

24

23

21

21

21

20

19.6

19.2

16.7

13.6

MAXIMUM BHP AT A GIVEN RPM = (RPM/715)

3

MAXIMUM RPM = 910

TIP SPEED (ft/min) = RPM x 6.414

MAXIMUM MOTOR FRAME SIZE = 184T

42

3

4

(1086)

*31

1

2

(800)

5

3

4

(146)

34

(864)