OM-491 Page 23

SECTION 6 − OPERATING AUXILIARY EQUIPMENT

6-1. 120 Volt And 240 Volt Duplex Receptacles

2

1

120 V 20 A AC GFCI Recep-

tacle GFCI1

2

240 V 20 A AC Receptacle

RC1

Receptacles supply 60 Hz single-

phase power at weld/power speed.
If a ground fault is detected, GFCI

Reset button pops out and

receptacle does not work. Check

for faulty tools plugged in

receptacle. Press button to reset

GFCI1.

.

At least once a month, run en-
gine at weld/power speed and

press test button to verify GFCI

is working properly.

3

Circuit Breaker CB1

4

Circuit Breaker CB2

5

Circuit Breaker CB3

CB1 and CB3 protect RC1 from

overload. If CB1 or CB3 opens,

RC1 does not work. 120 volts may

still be present at RC1. Press but-

ton to reset breaker.
CB2 protects GFCI1 from overload.

If CB2 opens, GFCI1 does not

work. Press button to reset breaker.

.

If a circuit breaker continues to
open, contact Factory Autho-

rized Service Agent.

Maximum output is 1.8 kVA/kW

from GFCI-1 and 3.6 kVA/kW from

RC1. Maximum output from all re-

ceptacles is 4 kVA/kW.

.

Auxiliary power is not affected
by weld output.

EXAMPLE: If 13 A is drawn from

RC1, only 7 A is available at GFCI1:
(240 V x 13 A) + (120 V x 7 A) = 4.0

kVA/kW