7-8. Diagnosing Causes Of Engine Fault Shutdowns

Ref. 191 631-A

Use the front panel engine lights to

help determine the cause of an au-

tomatic engine shutdown.

.

Correct the cause of the shut-
down before operating the

welding generator.

.

This unit does not have a bat-

tery charging fault shutdown.

The engine continues to run if

the Battery Charging Light

goes on.

Normal Condition:

Oil Pressure And Battery Charging Lights On;

Fuel And Temperature Lights Off.

If Oil Pressure Light Is Off, See Factory Authorized Service Agent.

If Battery Charging Light Is Off, Check Alternator And Belt.

If Temperature Light Is On, Correct Cause Of Overheating (See Engine Manual).

If Engine Is Okay, See Factory Authorized Service Agent.

If Fuel Light Is On, Check Fuel Level.

If Fault Continues, See Factory Authorized Service Agent.

Start Engine (With No Load Applied).

Continue Pressing Shutdown Switch

Until Engine Lights Go Off.

Normal Condition:

Engine Lights Go Off As Engine Reaches

Normal Operating Condition.

Lights That Stay On After 20 Sec. Indicate

Fault Condition.

Stop Engine And Correct Fault (See Above) If

Fault Continues, See Factory Authorized Ser-

vice Agent.

Turn Engine Control Switch To Run/Idle

Position While Pressing Magnetic Shut-

down Switch.

20s

Pre-Start Diagnostic Checks

Diagnostic Checks While Running