7-7. Overload Protection

Y Stop engine.

.

When a circuit breaker or fuse
opens, it usually indicates a

more serious problem exists.

Contact Factory Authorized

Service Agent.

1

Fuse F1

2

Fuse F2

F1 and F2 protect the stator exciter

winding from overload. If F1 opens,

weld and auxiliary power is low or

stops entirely. If F2 opens, weld out-

put is low or stops entirely. 4 kVA/

kW auxiliary power is still available.
3

Circuit Breaker CB10 (Not

Shown)

4

Circuit Breaker CB11

5

Circuit Breaker CB12

6

Circuit Breaker CB13

CB10 protects the engine battery

circuit. If CB10 opens, the engine

will not crank. CB10 automatically

resets when the fault is corrected.
CB11 protects the max OCV circuit.

If CB11 opens, the max OCV circuit

does not work and open circuit volt-

age is variable at all times (see max

OCV note under Weld Controls in

Section 5-2).
CB12 protects the field flashing cir-

cuit. If CB12 opens, the generator

may not excite at start-up and weld

and auxiliary power output may not

be available.
CB13 protects the engine shut-

down circuit. If CB13 opens, the en-

gine cranks but does not start.
Press button to reset breaker.