3 restrictions – MITSUBISHI ELECTRIC TG-2000A User Manual

Page 6

Advertising
background image

3

2.3 Restrictions

The following restrictions apply to the TG -2000A application.

(1) System configuration limits

Number of units

Notes

G-50A

M a x . 40 units

G-50A Ver. 2. 10 or higher

Indoor unit

Max. 50 units/G-50A Max. 2000 units (including all IC, KIC, AIC, LC, and FU)

[Symbol]IC: Indoor unit, LC: LOSSNAY, FU: OA processing unit, A IC: “A” controller,

KIC: “K” controller

(2) Group setting restrictions

Item

Restrictions

Note

Remote controls

2 per group

* Other remote controls besides M -NET

type will not work

Number of indoor units
connected to a group

1 to 16

* IC, AIC, KIC, or LC cannot be used

within the same group. It is not pos -
sible for group settings to span G-50A

Number of SC and RC
connected to a group

4 per group

* The number of G-50A is not included

Groups per floor

Max. 50 groups per floor Up to 50A groups can be displayed on

one floor of the whole building window.

*1 The ME remote controller and MA remote controller cannot be used together for the same group.
*2 Set the same function unit for the group.

[Symbol]SC: System controller, RC: Remote controller

(3) Block setting

• The block comes in two types, operation block and charge block.
• The operation block is an aggregate of groups, and it is possible to set a different model group

for the same operation block.

• The charge block consists of an aggregate of operation blocks.













(4) Notes on using K control models

When using a K transmission converter (model name: PAC-SC25KA, PAC-SC25KAA(-E)) to manage K
control models, take note of the following. See the documentation provided with the K transmission
converter for more detail.
• The address of the K transmission converter will be the smallest address of the K control model +

200.

• Set the K control model addresses so that they are larger than the M transmission model

addresses.

• When setting a group containing K control models, make the group number the same as the

smallest unit address in the group.

(5) Notes on using A control mode

• Use the A/M NET Adapter (model name: PAC-SF48MA(-E)). Set the group to “Group with only

A control”.

(6) Countermeasure when an error occurs

• Note that each control or function may not operate properly when rebooting (*1) or when a fault

occurs in the centralized Controller G-50A. Since each error is displayed when it occurs, it is
recommended to solve the faults quickly.

*1 Indicates that the system is restarting.