Calculating total duct length

Each of bends and differing
components of the dryer's venting
creates its own frictional resistance to
the flow of the exhaust air. This frictional
resistance is expressed in a
comparative duct length
. The
comparative duct length indicates the
length of a smooth straight pipe (of the
same diameter), producing the same
resistance to air flow as the original
ducting component (Table I).

Adding together the comparative duct
lengths of all components reveals the
total duct length. The total duct length
is a calculated value that compares
how long a smooth straight venting
pipe would have to be for the same air
flow.

Since an internal pipe diameter
strongly affects flow's resistance, a vent
with a total duct length exceeding 20
m
requires a larger diameter (Table II).

Procedure

1. Measure the distance requiring

straight ducting. Multiply this value
by the corresponding comparative
pipe length from Table I.

2. Determine the number of bends and

components required. Add their
comparative lengths together using
Table I.

3. Add together all the comparative

lengths thus determined: Thus you
obtain the total duct length.

4. From Table II, determine which

internal duct diameter is required for
the total duct length.

Table I

Components

Comparative duct length

Flexible ducting

1 m laid straight

45° bend
(Bend radius = 0.25 m)

90° bend
(Bend radius = 0.25 m)

1.8 m
1.5 m

2.5 m

Vent hose(flexible or Alu-Flex)

1 m laid straight or 1 m straight
pipe

45° bend
(Bend radius = 0.25 m)

90° bend
(Bend radius = 0.25 m)

1.0 m

0.6 m

0.8 m

Wall vent kit or window vent kit

with grill insert

with non-return flap (hinged flap)

3.8 m
1.5 m

Non-return flap* for integration
into the vent ducting
(see section "

d Vent collector

duct")

14.3 m

Flat duct (for stacked
arrangement)

11.0 m

Left or right dryer vent opening

1.0 m

* Miele accessory available on order

Table II

Maximum permissible

total duct length

Diameter required

20 m
40 m

100 m

100 mm
125 mm
150 mm

Installing the dryer vent