3-9. Electrical Service Guide

Actual input voltage should not exceed

±

10% of indicated required input voltage. If

actual input voltage is outside of this range, output may not be available.

NOTE

50/60 Hz Three Phase

Input Voltage

400

Input Amperes At Rated Output

17

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

20

Normal Operating

3

25

Min Input Conductor Size In mm

2

,

4

2.5

Max Recommended Input Conductor Length In Meters

41

Min Grounding Conductor Size In mm

2

,

4

2.5

Reference: 1999 National Electrical Code (NEC)

1 Consult factory for circuit breaker applications.

2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

3-10. Connecting Input Power

Y Always connect green/yel-

low wire to supply ground-

ing terminal, never to a line

terminal.

Check input voltage available at

site.
1

Input And Grounding

Conductors

2

Line Disconnect Device

Select type and size of overcurrent

protection using Section 3-9.

Tools Needed:

L1

2

1

L2
L3

Y Always connect grounding

conductor first.

= GND/PE

Green/Yellow

Advertising