3-15. Selecting A Location And Connecting 3-Phase Input Power

Ref. 803 543-D / 803 766-A

!

Installation must meet all National and
Local Codes - have only qualified
persons make this installation.

!

Disconnect and lockout/tagout input
power before connecting input
conductors from unit.

!

Always connect green or green/yellow
conductor to supply grounding terminal
first, and never to a line terminal.

!

Warning: This unit is either a
200/230/460 ac input voltage model or
460/575 ac input voltage model. See
rating label on unit and check voltage

available at site to be sure it matches
the voltage specified on the rating
label.

1

Rating Label

2

Input Power Cord

3

Disconnect Device (switch shown in
the OFF position)

4

Green Or Green/Yellow Grounding
Conductor

5

Disconnect Device Grounding Terminal

6

Input Conductors (L1, L2 And L3)

7

Disconnect Device Line Terminals

Connect green or green/yellow grounding

conductor to disconnect device grounding
terminal first.

Connect input conductors L1, L2, and L3 to
disconnect device line terminals.

8

Over-Current Protection

Select type and size of over-current
protection using Section 3-13 (fused
disconnect switch shown).

Close and secure door on disconnect device.
Remove lockout/tagout device, and place
switch in the On position.

Tools Needed:

2

1

Rear Panel

18 in (457 mm)

for airflow

!

Do not move or operate
unit where it could tip.

= GND/PE Earth Ground

3

3

4

5

7

6

8

L1
L2
L3