OM-815 Page 7

4-3.

Welding Power Source Input Power Connections

WARNING

ELECTRIC SHOCK can kill.

Do not touch live electrical parts.

Turn Off welding power source, and disconnect input power to rack before inspecting or installing.

Have only qualified persons install unit.

Installation must meet National Electrical Code and all other codes.

swarn3.1* 2/93

When installing conductors from the welding power source, torque the Power
circuit breaker terminals and grounding terminal to 40 in-lbs (4.5 N·m).

NOTE

Have only qualified persons make this instal-
lation.
1

Control Box

2

Access Door

Open access door with same number as
welding power source location.
3

Welding Power Source Input Power
Cord

4

Strain Relief Connector

Insert input power cord through strain relief
into entry hole for opened access door.

5

Grounding Conductor – Green Or
Green With Yellow Stripe(s)

6

Input Conductors

7

Power Circuit Breaker Terminals

8

Grounding Terminal

Install input conductors from welding power
source to Power circuit breaker.

Install grounding conductor to grounding
terminal.

Close and secure access door.

ST-158 333 / ST-151 269-B

1

Tools Needed:

2

5

8

4

3

6

7

Figure 4-3. Welding Power Source Input Power Connections

Table 4-1. Weld Cable Size*

Total Cable (Copper) Length In Weld Circuit Not Exceeding

100 ft (30 m) Or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Welding

Amperes

10 To 60%

Duty Cycle

60 Thru 100%

Duty Cycle

10 Thru 100% Duty Cycle

100

4

4

4

3

2

1

1/0

1/0

150

3

3

2

1

1/0

2/0

3/0

3/0

200

3

2

1

1/0

2/0

3/0

4/0

4/0

250

2

1

1/0

2/0

3/0

4/0

2-2/0

2-2/0

300

1

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

350

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

2-4/0

400

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-4/0

2-4/0

500

2/0

3/0

4/0

2-2/0

2-3/0

2-4/0

3-3/0

3-3/0

600

3/0

4/0

2-2/0

2-3/0

2-4/0

3-3/0

3-4/0

3-4/0

700

4/0

2-2/0

2-3/0

2-4/0

3-3/0

3-4/0

3-4/0

4-4/0

800

4/0

2-2/0

2-3/0

2-4/0

3-4/0

3-4/0

4-4/0

4-4/0

900

2-2/0

2-3/0

2-4/0

3-3/0

3-4/0

4-4/0

4-4/0

1000

2-2/0

2-3/0

2-4/0

3-3/0

4-3/0

4-4/0

1250

2-3/0

2-4/0

3-3/0

4-3/0

4-4/0

1500

2-4/0

3-3/0

3-4/0

4-4/0

*Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.