OM-815 Page 10

4-6.

Connecting Input Power To Rack

WARNING

ELECTRIC SHOCK can kill.

•

Do not touch live electrical parts.

•

Turn Off welding power sources before inspecting or installing rack.

•

Have only qualified persons install rack.

•

Installation must meet National Electrical Code and all other codes.

swarn3.1* 2/93

Have only qualified persons make
this installation.

1

Rear Control Box Center

2

Access Panel

Remove access panel.

3

Line Disconnect Device Of
Proper Rating

4

Input Conductors

5

Grounding Conductor

Select size and length using
Table 4-2. Conductors must be
able to carry the combined amper-
age draw of all welding power
sources mounted on the rack. Con-
ductor insulation must comply with
national, state, and local electrical
codes. Use lugs of proper amper-
age capacity and correct hole size.

6

User-Supplied Strain Relief
Connector

Insert conductors through strain
relief.

7

Input Terminal Block

8

Line Terminals

9

Ground Terminal

Connect grounding conductor to
ground terminal first. Then connect
input conductors to line terminals.

Reinstall access panel.

Install grounding conductor and in-
put conductors in conduit or equiv-
alent to deenergized line discon-
nect device.

Connect grounding conductor first,
then line input conductors.

Be sure grounding conductor goes
to an earth ground.

10 Overcurrent Protection

Select type and size using
Table 4-2. Install into deenergized
line disconnect device (fused
disconnect switch shown).

1

2

7

8

4

6

9

5

3

10

ST-151 270-C

5

Figure 4-6. Input Power Connections