SECTION 6 − OPERATING AUXILIARY EQUIPMENT

6-1. 120 Volt And 240 Volt Duplex Receptacles

Ref. ST-180 933-B

3

2

Y If unit does not have GFCI

receptacles, use GFCI-pro-

tected extension cord.

1

120 V 15 A AC Receptacle

RC2

2

240 V 15 A AC Receptacle

RC1

Receptacles supply 60 Hz single-

phase power at weld/power speed.
3

Circuit Breakers CB1 And

CB2

CB1 and CB2 protect RC1 and

RC2 from overload. If CB1 or CB2

opens, RC1 and one half of RC2

does not work. 120 volts may still

be present at RC1. Press button to

reset breaker.

.

If a circuit breaker continues to
open, contact Factory Autho-

rized Service Agent.

Maximum output from each duplex

receptacle is 1.8 kVA/kW, and 3

kVA/kW from all receptacles.

.

Auxiliary power is not affected

by weld output.

EXAMPLE: If 10 A is drawn from

RC1, only 5 A is available at RC2:
(240 V x 10 A) + (120 V x 5 A) = 3.0

kVA/kW