4-13. Selecting A Location And Connecting Input Power

804 912-A

L1

L2

230 VAC, 1

18 in (457 mm) of
space for airflow

!

Do not move or operate
unit where it could tip.

3

!

Installation must meet all National
and Local Codes − have only qualified
persons make this installation.

!

Disconnect and lockout/tagout input
power before connecting input con-
ductors from unit.

!

Always connect green or green/yel-
low conductor to supply grounding
terminal first, and never to a line ter-
minal.

!

Special installation may be required
where gasoline or volatile liquids are
present − see NEC Article 511 or CEC
Section 20.

1

Rating Label

Supply correct input power.

2

Plug (NEMA Type 6-50P)

3

Receptacle
[NEMA Type 6-50R (Customer
Supplied)]

4

Input Power Cord.

Connect directly to line disconnect device if
hard wiring is required.

5

Black And White Input Conductor (L1
And L2)

6

Green Or Green/Yellow Grounding
Conductor

7

Disconnect Device (switch shown in
the OFF position)

8

Disconnect Device Grounding Terminal

9

Disconnect Device Line Terminals

Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.

Connect input conductors L1 and L2 to
disconnect device line terminals.

10 Over-Current Protection

Select type and size of over-current
protection using Section 4-12 (fused
disconnect switch shown).

Connect plug to receptacle if hard wiring
method is not used.

Close and secure door on disconnect device.
Remove lockout/tagout device, and place
switch in the On position.

1

2

4

1

=GND/PE Earth Ground

7

L1

L2

6

5

8

9

10