10. electrical service guide – Miller Electric Axcess 300 User Manual

Page 26

Advertising
background image

OM-230 032 Page 20

4-10. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

NOTICE − INCORRECT INPUT POWER can damage this welding power source. This welding power source requires a CONTINUOUS supply of
input power at rated frequency

(+

10%) and voltage

(+

10%). Phase to ground voltage shall not exceed +10% of rated input voltage. Do not use a genera-

tor with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.

.

Actual input voltage should not exceed

±

10% of indicated required input voltage. If actual input voltage is outside of this range, output may not

be available.

Three

Phase

50/60 Hz

Input Voltage

400

Input Amperes At Rated Output

10.4

Max Recommended Standard Fuse Rating In Amperes

Circuit Breaker

1

, Time-Delay

2

10

Normal Operating 3

15

Min Input Conductor Size In AWG

4

14

Max Recommended Input Conductor Length In Feet (Meters)

223

(68)

Min Grounding Conductor Size In AWG

4

14

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

Advertising