Dasd checkout, Bus fault messages, Temperature related system shutdown – IBM xSeries 330 User Manual

Page 105: Dasd checkout bus fault messages

Advertising
background image

Chapter 7. Symptom-to-FRU index

97

Temperature related system shutdown

DASD checkout

Bus fault messages

System shutoff due to "X" V over voltage

(level-critical; system shutoff due to "X"
supply over voltage)

1.

Check power supply connectors

2.

Replace power supply

System shutoff due to "X" V under voltage

(level-critical system shutoff due to "X"
supply under voltage)

1.

Check power supply connectors

2.

Replace power supply

System shutoff due to VRM "X" over
voltage

1.

Replace power supply

Message

Action

System shutoff due to board over
temperature

(level-critical;

board is over temperature)

1.

Ensure system is being properly cooled

, see “Temperature

checkout” on page 26.

2.

Replace system board

System shutoff due to CPU "X" over
temperature

(level-critical; CPU "X" is

over temperature)

1.

Ensure system is being properly cooled

, see “Temperature

checkout” on page 26.

2.

Replace CPU "X"

System shutoff due to CPU "X" under
temperature

(level-critical; CPU "X" is

under temperature)

1.

Ambient temperature must be within normal operating
specifications,

see “Features and specifications” on page 4.

2.

Replace CPU "X"

System shutoff due to DASD temperature
(sensor X)

(level-critical;

DASD area reported temperature outside
recommended operating range)

1.

Ensure system is being properly cooled

, see “Temperature

checkout” on page 26.

2.

Replace SCSI Backplane

System shutoff due to high ambient
temperature

(level-critical; high

ambient temperature)

1.

Ambient temperature must be within normal operating
specifications

, see “Features and specifications” on page 4.

2.

Replace Front Panel Assembly

System shutoff due to system board under
temperature

(level-critical; system

board is under temperature)

1.

Ambient temperature must be within normal operating
specifications

, see “Features and specifications” on page 4.

2.

Replace System Board

Message

Action

Hard drive "X" removal detected

(level-critical; hard drive "X" has been
removed)

1.

Information only, take action as appropriate.

Message

Action

Failure reading I2C device.

Check devices

on bus 0.

1.

Replace system board

Message

Action