8. FUNCTION

8-1. Room Temperature Control

Room temperature control is obtained by cycling the compressor ON and OFF under control of the room

temperature sensor in the remote control unit.

The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to

the controller in the indoor unit.

The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at

least 3 minutes. To protect the compressor from stalling out when trying to start against the high side

refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to

equalize.

As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of com-

pressor operation.

Thermo ON : When the room temperature is above T + 2°F (T°F is set temperature).

Compressor

ON

Thermo OFF : When the room temperature is equal to or below set temperature T°F.

Compressor

OFF

Set temp.

T+2

°

F

Signal from remote control unit

Room temp.

More than

5 minutes

Thermo
OFF

Indoor fan

Outdoor fan

Compressor

Set speed

ON

ON

ON

OFF

OFF

OFF

ON

OFF

ON

ON

OFF

OFF

3 minutes

5 minutes

3 minutes

3 minutes

3 minutes

3 minutes

3 minutes

3 minutes

3 minutes

Thermo
ON

Thermo
OFF

Thermo
ON

Thermo
ON

Thermo
ON

Thermo
OFF

T

°

F

000-215 SM (1-56) 7/5/00 2:49 PM Page 41