9-3-3. Only compressor does not run

9-3-4. Only flap motor does not run

9-3-5. Function of outdoor fan speed control does not work properly.

(CLxx5x models only)

Measure resistance of
compressor motor winding.

•

Measure power supply
voltage.
The voltage is too low.

•

NO

Check compressor motor
capacitor.

•

Either internal protector or
overload relay is working.

•

Temperature of compressor
is abnormally high.

•

YES

YES

YES

NO

Refrigerant gas shortage.

Charge refrigerant gas (R22).

Rotor may be locked up.

Measure resistance of flap
motor winding. (FLP)

•

• Check controller in outdoor unit.

(POW-CL125)

• Check outdoor air thermister in
outdoor unit.

(TH)

Refer to 8-4 "Outdoor Fan Speed Control."