Lincoln Impringer Conveyor Oven 1200 User Manual
Page 32
 
Impinger I -–1000 Series Service Manual - International
32
Ignitor/Sensor Assembly
Check for visible damage to ignitor/ sensor 
assembly. If there is no visible damage to the 
components, and no spark, replace the spark 
generator. If there is visible damage to the Ignitor 
sensor assembly, replace it. Also check for frayed 
or damaged wires in burner tube. 
Gas Valve
Check for 220 VAC supply to gas valve. If no 
voltage present, check reset button on ignition 
control, check all connections for tightness. If there 
still is no voltage at gas valve, replace 
No Pilot
Solenoid Valve
If all above are operating properly, but there is no 
pilot flame, check for any obstructions in bypass 
orifice (drilled port through wall inside solenoid 
valve). 
Pilot flame, but burner 
will not stay ignited 
Flame Sensor
(There should be a visible pilot flame at this time.) 
To check for flame sensor operation, connect a 
digital multimeter (capable of measuring D. C. 
micro amperes) between the flame sensor wire and 
terminal "F" on the ignition control or in flame 
sensor lead for Landis & Gyr. NOTE: this is a 
current measurement and the meter must be 
connected in series. Proper current readings 
should be between 2 and 4 micro Amp. D.C. for 
Honeywell, 3 micro amp for Landis & Gyr minimum. 
If these readings are not achieved, replace 
ignitor/sensor assembly. Also check for any type of 
damage to flame sensor wire and connections. 
Ignition Control If there is sufficient flame sensor 
current, but the burner will not remain ignited, 
check reset button on ignition control, if all above 
are okay, replace ignition control. 
Temperature Control
Check for 120 VAC across L1 and L2 on 
temperature control board. If no voltage present, 
retrace wiring back to power supply. Turn the 
temperature adjustment knob to the maximum 
temperature position and check for 120 VAC at the 
load terminal to neutral. If 120 VAC is not present, 
proceed as follows: If 120 VAC is present and unit 
is not heating, see "Solenoid Valve." 
Thermocouple Probe
Remove thermocouple leads from the temperature 
control board and measure the millivolt output of 
these leads. Refer to chart on page 59 for proper 
readings. 
Temperature Control 
Potentiometer 
WITH POWER OFF: remove the leads from the 
temperature control board and measure ohms from 
black and white leads. The ohm reading should be 
0 to 2.5K ohms as the dial is turned through its full 
rotation. From black to red leads the reading should 
be 2.5K ohms and remain steady throughout the 
full rotation of the dial. If the thermocouple probe 
and the control potentiometer check good, then the 
problem is usually with the temperature control 
board. 
Red indicator light is 
on but no main flame 
Solenoid Valve
If output voltage is present at temperature control 
board, check for voltage at solenoid valve. If 
voltage is present, listen for valve to open and 
close. Also check for opens and shorts in coil. 
Replace as needed.