Lincoln Impringer Conveyor Oven 1200 User Manual
Page 33
 
Impinger I -–1000 Series Service Manual - International
33
Intermittent heating
As Follows
Both the main fan motor and burner blower motor 
are equipped with thermal protection and will cease 
to operate if overheating occurs. This can cause 
the units to cycle on and off intermittently. This may 
be caused by improper ventilation. Also most of the 
problems listed under "oven will not heat" can 
cause intermittent failure. 
Voltage Supply
Check incoming voltage supply at line 1 to neutral. 
There should be a voltage reading of 120 VAC. If 
not present, check breakers. 
3 Amp Fuse
This conveyor fuse is located on the front panel. 
Replace if defective. 
Fuse Holder Conveyor Switch Check and/or Replace. Same procedure as for fan
switch.
D. C. Motor Control Board
Check for 120 VAC input to D. C. control board 
across L1 and L2. Check the 3 amp fuse on the D. 
C control board. Check for D.C. voltage at terminal 
F1 and F2. Voltage should be 100 VDC ± 10 
steady. If this voltage is not present, replace D. C. 
control board. Check for D. C. voltage output to the 
motor across terminals A1 and A2 (this voltage 
should be approx. 125 VDC at maximum conveyor 
motor speed). 
Speed Control Potentiometer
This is a 0 to 400 ohm or 0 to 500 ohm, 10-turn 
potentiometer. WITH POWER OFF: remove the 
red, white, and black leads from terminals S1, S2, 
S3. With a digital multimeter, check the ohm 
reading across the red to black leads. This ohm 
reading should be a steady 400-ohm, or 500-ohm, 
through the entire 10-turn rotation of the 
potentiometer. Red to white, should be 0-400 or 0-
500 ohms as the pot. is rotated. Check for shorts or 
opens or unsteady, ohm reading, if potentiometer is 
defective, replace. If the potentiometer checks OK, 
and 
there is no output at terminals A1 and A2, replace 
the D.C. control board. 
Reversing Switch
If there is D. C. voltage output from the motor 
control board, but the conveyor drive motor is not 
running, check the D.P.D.T. reversing switch.
Conveyor will not run 
(S/N 100-4389) 
Conveyor Drive Motor
Check the conveyor drive sprocket for tightness. 
Disconnect the motor, check the red and black 
motor leads for opens, shorts or grounds. Check 
the brushes for excessive or 
abnormal wear.
Replace as needed. Reconnect motor. Test for 
operation. If motor does not run, replace. 
Voltage Supply
Check incoming voltage supply at line 1 to neutral. 
There should be a voltage reading of 120 VAC. If 
not present, check breakers. 
3 Amp Fuse
This conveyor fuse is located on the front panel. 
Replace if defective. 
Fuseholder
Check and/or Replace
Fan Switch
See procedure for checking on page 26.
Conveyor will not run 
(S/N 4390 to Q14974 
1000 Series 
S/N 4390-Q14790 
1200 Series) 
Conveyor Switch
Same procedure as for fan switch.
NOTE:
(Dual Belt Ovens)
Dual belt ovens utilize 2 complete independent 
conveyor drive systems. The trouble shooting 
procedures are the same as single belt ovens, 
except that the dual belt ovens use one each of the 
following: one "A" DC. control board and one "B" D. 
C. control board.