24 Specifications

3.7.3

Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48

The electrical specifications of the Helios Rectifiers 200I/48 and 200E/48 are listed in Table 27.

3.7.4

Standards

The following standards also apply to the rectifiers:

• ANSI Std. C62.41/IEEE Std. 587-1980, Class A and B lightning surge 6000 V, 3000 A, 1.2 x 50

ms impulse, 10 hits per second

• ANSI Std. C82.41 oscillatory surge 2500 V, 0.5 ms impulse, 100kHz positive/negative oscillat-

ing decay

• Bellcore TR-TSY-000947
• IEC-950, VDE EN 60950, EN 41003
• CISPR 22, Class A
• CE mark

Table 27

Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48

Parameter

Specification

Input voltage

Helios Rectifier 200I/48:

380/415 V AC, three phase, 47-63 Hz
Input voltage range: 330 to 475 V AC

Helios Rectifier 200E/48:

480 V AC, three phase, 47-63 Hz
Input voltage range: 430 to 520 V AC

Input current

Helios Rectifier 200I/48: 18.3 A RMS nominal at 380 V AC input and -54 V DC, 200 A
output (24 A RMS worst case)
Helios Rectifier 200E/48: 15 A RMS nominal at 480 V AC input and -54 V DC, 200 A
output (17 A RMS worst case)

Input protection

A 3 pole / 25 A circuit breaker opens all three lines.

Recommended AC
service input

30 A, 3 pole AC circuit breaker

Output voltage

Float: -46 to -58 V DC
Equalize: 0 to 4 V DC above Float
Maximum: -60 V DC

Output current

200 A nominal
Adjustable between 100 and 210 A

Output protection

The rectifier is protected by a 250 A circuit breaker at the output.
The output current is limited to a value adjustable from 50% to 105% of the rated
capacity of the rectifier. This circuit is factory set to 205 A.

Output regulation

The rectifier output voltage is automatically regulated to remain within ±0.5% of the
selected value under all load conditions and within the specified input voltage,
frequency, and ambient temperature ranges. And within + 1% for any combinations of
specified input, output and environmental conditions.

Efficiency

Efficiency is better than 89% at nominal input voltage and an output load greater than
80 A.

Power factor

Power factor is better than 0.99 at nominal input voltage and an output load greater
than 80 A.

Electromagnetic
interference (EMI)

The rectifier meets the FCC requirements for conducted and radiated EMI for Class
“B” equipment.

Heat dissipation

1,335 W (4,558 Btu/hr) at -54 V DC, 200 A output

Total harmonic
distortion (THD)

THD is less than 5% between half load and full load at nominal input voltage