Tools required, Notice, Caution – Liebert Cooling Modules XDH User Manual

Page 25

Advertising
background image

Piping

21

Figure 21 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe

5.10 Disconnecting a Liebert XDH With Liebert XD Flex Pipe From a Liebert XD System

NOTICE

Before uninstalling a Liebert XDH with Liebert Flex Pipe from the prefabricated piping

mains: Close the supply service valve, wait approximately two minutes, then close the return

service valve.
Read all instructions before beginning.

Tools Required

• Two adjustable wrenches, maximum adjustment size of 2-1/2 inches
• Phillips head #2 screwdriver

1. Close the service valves in the supply line to the Liebert XDH (smaller couplers).
2. Close the service valves in the return lines to the Liebert XDH (larger couplers).
3. Locate and have ready the caps and plugs for both ends of the supply and return couplers.
4. Loosen the female supply couplers from the male supply couplers (smaller couplers). This

requires two adjustable wrenches. Refer to Figure 20.

5. The Liebert XDH side of the female couplers must be held stationary while the collars on the

couplers are being loosened. Refer to Figure 20.

6. Disconnect the couplers.

!

CAUTION

Risk of sudden discharge of pressurized refrigerant. Can cause equipment damage or injury.
Do not disconnect threaded refrigerant couplers at the unit cabinet end without relieving

system pressure. Reclaim any refrigerant during removal of unit from system.

Return Service Valve
Make sure valve is
open after system
leak check

Supply Service Valve
Make sure valve is
open after system
leak check

Return Liebert
Flex Pipe

Supply Liebert Flex Pipe

Return
Main

Supply Main