0 electrical, 1 connecting high voltage wiring, Figure 24 liebert xdh electrical connections – Liebert Cooling Modules XDH User Manual

Page 27: Lectrical, Connecting high voltage wiring, Warning

Advertising
background image

Electrical

23

6.0

E

LECTRICAL

The unit must be installed in accordance with national wiring regulations. Refer to the unit’s serial

tag for electrical requirements. Refer to Table 3 for details.

6.1

Connecting High Voltage Wiring

The Liebert XDH requires single-phase power for normal operation. The unit ships with two power

cords, each 10 feet (3m) long with NEMA 5-15 plugs, which connect to common, three-prong outlets

(see Figure 24).
The XDH will function properly with only one power cord. The second power cord permits connection

to a separate power source to increase reliability—If one power source fails, the cord connected to the

remaining, live power source will power both banks of fans.
To attach the power cords, clip the plastic hangers attaching the cords to the Liebert XDH. Press the

appropriate end of each cord onto the electrical inlet. Attach the strain-relievers onto the power cords

and press the assemblies into the cable exit slots.

Figure 24 Liebert XDH electrical connections

!

WARNING

Risk of electric shock. Can cause death or injury.
Disconnect both electric power cords before working within the unit.

Power Cord Strain Relievers

Rear of Liebert XDH

Panel Removed for Clarity

Condensate Detection
Dry Contacts-Low Voltage
Connections
(Upper Circuit 84, 85)

Condensate Detection
Dry Contacts-Low Voltage
Connections
(Lower Circuit 82, 83)

IEC Primary
Power Inlet

IEC Secondary
Power Inlet

60Hz MODELS ONLY

Field wiring connections

at terminal strip to be NEC

Class 2. Use switch contacts

with 75VA minimum rating.

50Hz MODELS ONLY

Field wiring connections

at terminal strip for safety extra

low voltage circuits only. Use

switch contacts rated 75VA

minimum, 24VAC maximum.