The Liebert XDH’s controls are on the front of the unit at the Liebert XDH’s midline for easy access.

Each switch controls the operation of one bank of three fans (see Figure 26). The separate switches

permit the use of only one bank of fans at a time, reducing the airflow if the Liebert XDH’s full cooling

capacity is not needed.

Figure 26 Fan switches

8.1

Start the Liebert XDH

The Liebert XDH’s fans must be on before starting the Liebert XDP or Liebert XDC that will supply

refrigerant to the Liebert XDHs.
To start the Liebert XDH, press either of the rocker switches to turn on one or both of the Liebert

XDH’s banks of fans. Pressing the left switch starts the fans in the upper half of the Liebert XDH; the

right switch, the lower fans.
The refrigerant sources, either Liebert XDP or Liebert XDC, must be started separately.

NOTE
At least one of the Liebert XDH’s banks of fans must be turned on before either the Liebert XDP

or Liebert XDC is switched on.
At least one of the Liebert XDH’s banks of fans must be operating at all times that the Liebert

XDP or Liebert XDC is operating. Operating either the Liebert XDP or the Liebert XDC without

at least one of the Liebert XDH’s banks of fans rotating may cause a system malfunction.

Upper Fan Bank Switch

Lower Fan Bank Switch